Description
Applications:
Overvoltage, Undervoltage, and overcurrent protection for household equipment.
Function Features:
-Voltage / current monitoring and protection.
-Double bus wiring design has a stronger ability.
-Over/under voltage value and over-current value can be set.
-Self-reset after the fault.
-Digital display voltage, current value, and fault status can be displayed by LED.
-1-MODULE, DIN rail mounting.
| GPS8-03 | |
| function | Overvoltage, under-voltage, and over current |
| Rated supply voltage | AC220V(L1,L2,L3-N) |
| Rated supply frequency | 50/60HZ |
| Rated operational current | 63A (AC1) |
| Burden | AC max.3VA |
| Voltage display | √ |
| Current display | √ |
| Overvoltage operation value | 230V~300V(factory default: 275V) |
| Overvoltage action delay | 0.5s |
| Under voltage operation value | 145V~210V(factory default: 175V) |
| Under voltage action delay | 0.5s |
| Overcurrent operation value | 1 A~63A(factory default: 63A) |
| Overcurrent action delay | 3s~600s |
| Voltage unbalance value | 20V~99V(factory default: 40V) |
| Voltage unbalance action time | 10s |
| Power-up delay | 2s |
| Reset time | 2~900s(factory default:30s) |
| Measurement error | <1% |
| Operating temperature | -20°C to +55°C (・4°Fto131°F) |
| Storage temperature | -35°Cto+75°C (-22T to 158°F) |
| Mounting/DIN rail | Din rail EN/IEC 60715 |
| Protection degree | IP40 for front panel/IP20 terminals |
| Operating position | any |
| Overvoltage cathegory | III. |
| Pollution degree | 2 |
| Dimensions | 82X72X68mm |
| Weight | 130g |