GYM9H-125DC 250V-1000V DC Miniature Circuit Breaker 1P-4P

The GYM9H-125DC dc miniature circuit breaker from GEYA is a high-performance DC protection device engineered to safeguard direct current systems from overloads, short circuits, and other electrical faults. Tailored for applications in communication and photovoltaic (PV) systems, this MCB ensures reliable and safe operation. Certified to IEC/EN60947 and GB/T 14048.2 standards, it’s the trusted choice for your DC system protection needs.

  • Pole Options: Available in 1P, 2P, 3P, and 4P configurations.
  • Rated Voltage (Ue):  1P: 250VDC,2P: 500VDC, 3P: 750VDC,4P:1000VDC
  • Short-Circuit Capacity:Icu (Ultimate): 6000A,Ics (Service): 6000A
  • Rated Current (In): Available in 63A, 80A, 100A, and 125A to match diverse load requirements.

 

Category

Description

Product Highlight:

  • Compliant with International Standards: The GYM9H-125DC MCB adheres to IEC/EN60947 and GB/T 14048.2 standards, ensuring exceptional reliability and safety for global applications.
  • Versatile Configuration Options: Available in configurations ranging from 1P to 4P, with voltage support from 250VDC to 1000VDC and current ratings from 63A to 125A, this product adapts seamlessly to a wide variety of DC system needs.
  • High Breaking Capacity and Precise Tripping: With a 6000A short-circuit breaking capacity and three tripping curves (B, C, D), it delivers precise and reliable protection tailored to different load types.
  • User-Friendly Design: Equipped with a contact position indicator, support for up to 35mm² wiring capacity, and temperature compensation, it simplifies both installation and maintenance processes.

Performance Characteristic:

Test Test Current Initial Condition Limits of tripping or non-tripping time Result to be obtained Remarks Fiducial temperature
B、C、D

 

 

1.05In Cold t≤1h(In≤63) No Tripping 30℃
1.3In Immediately following t<1h(In≤63) Tripping Current steadily increased within 5s
2.55In Cold 1s<t<60s(In≤32A)

1s<t<120s(In>32A)

Tripping
B 4.8In Cold t≤0.1s No Tripping
C 6.8In
D 9.6In
B 7.2In Cold t<0.1s Tripping
C 10.2In
D 14.4In

Temperature Compensation:

When the ambient temperature is not the baseline temperature of 30 , the reference ℃
correction coefficient is as follows:

Ambient Temperature -20℃ -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 60℃
Current Correction Factor 1.25 1.2 1.15 1.10 1.05 1.00 0.95 0.90 0.85

Wiring Diagram:

Wiring Diagram

Outline Overall and Installing Dimensions:

Outline Overall and Installing Dimensions

 

Contact Us
Contact Us

Check Out The Full Catalog

Quick Info Exchange Helps Us Serve You Better
(Low-voltage and solar energy electrical components catalog)

Electrical Equipment catalog