Description
The GYM9H-125-ZW DC circuit breaker is designed for DC applications with a rated voltage up to 1000V and a rated current up to 125A. It provides precise overload and short-circuit protection, and is suitable for infrequent manual switching operations in DC power systems.
This breaker is widely used in:
-
Photovoltaic (PV) power generation systems
-
Communication base stations
-
Industrial DC control systems
-
DC distribution panels
It complies with IEC/EN 60947-2 and GB/T 14048.2 standards and meets RoHS 2.0 environmental requirements.
Key Features
-
Non-polar DC design for flexible wiring
-
Rated voltage up to 1000V DC
-
Rated current options: 63A / 80A / 100A / 125A
-
Breaking capacity: 10kA
-
Contact position indication
-
Mechanical Life: 20,000 operations
-
Electrical Life: 1,500 operations
-
Installation on TH35-7.5 standard DIN rail
Tripping Curves

Temperature Derating Coefficient Table
| Ambient Temperature | Correction Factor |
|---|---|
| -20°C | 1.25 |
| -10°C | 1.20 |
| 0°C | 1.15 |
| 10°C | 1.10 |
| 20°C | 1.05 |
| 30°C | 1.00 |
| 40°C | 0.95 |
| 50°C | 0.90 |
| 60°C | 0.85 |
Tripping Characteristics
| Tripping Type | Current (A) | Starting Condition | Starting Time | Expected Result | Standard Temperature |
|---|---|---|---|---|---|
| B, C, D | 1.05In | Cold | t ≥ 1h (In ≤ 63), t ≥ 2h (63 < In ≤ 125) | No Trip | 30°C |
| B, C, D | 1.3In | Hot | t ≤ 1h (In ≤ 63), t ≤ 2h (63 < In ≤ 125) | Trip | 30°C |
| B, C, D | 2.55In | Cold | 1s < t < 120s | Trip | 30°C |