GYM9H-10KA Miniature Circuit Breaker(1~4 Poles)

A high-breaking-capacity 10kA miniature circuit breaker for AC 50/60Hz distribution circuits — engineered to deliver reliable overload and short-circuit protection in industrial, commercial, high-rise and residential installations.

  • Rated Current (In): 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 A
  • Rated Voltage (Ue): 1P: 230/400V (240/415V) · 2P–4P: 400V (415V) AC
  • Breaking Capacity (Icn): 10 kA per IEC/EN 60898-1
  • Tripping Curves: B, C, D
  • Poles: 1P / 2P / 3P / 4P
  • Operating Frequency: 50 / 60 Hz
  • Mechanical Life: 20,000 ops · Electrical Life: 10,000 ops
  • Standards: IEC/EN 60898-1, GB/T 10963.1 · RoHS 2.0
  • Certifications: CE / CB / SAA
  • 18 mm per pole · 35 mm DIN-rail mounting · IP20
  • Cost-effective alternative to tier-1 brand 10kA MCBs — same endurance, far better value

certificates

SKU GYM9H-10KA Categories ,

Description

GYM9H-10kA Miniature Circuit Breaker — Overview

The GYM9H-10kA MCB is a high-performance 10kA miniature circuit breaker (10kA circuit breaker) designed for AC 50/60Hz circuits with rated voltage up to 240/415V and rated current up to 63A, providing reliable overload and short-circuit protection together with circuit isolation. Compliant with IEC/EN 60898-1 and GB/T 10963.1 and certified by CE / CB / SAA, the GYM9H-10kA is suitable for industrial facilities, commercial buildings, high-rise structures and residential applications where a 10kA breaking capacity MCB, B/C/D tripping curves and a compact 18 mm-per-pole DIN-rail format are required.

The GYM9H Value Proposition:

GYM9H-10kA matches premium tier-1 10kA MCBs on the metrics that matter most for daily operation — 10,000-cycle electrical life, 20,000-cycle mechanical life, IEC/EN 60898-1 10kA breaking capacity and B/C/D curves — while delivering a dramatically more economical total cost of ownership. For projects where every panel position counts, GYM9H-10kA gives you certified high-breaking performance without the premium-brand price tag.

Key Features

  • High performance: Up to 10 kA breaking capacity and rated currents up to 63 A.
  • Compact solution: 1 standard module (18 mm) per pole — installs directly onto 35 mm DIN rail (TH35-7.5).
  • Full electrical isolation in compliance with IEC 60898 — safe disconnection for downstream maintenance.
  • Expandability: Accepts a wide range of optional accessories including auxiliary contacts, alarm contacts, shunt trip, under-voltage release and remote / motorized operating mechanisms.
  • Dual busbar connection for flexible, efficient wiring in distribution boards.
  • Transparent ID window and contact-position indicator for at-a-glance status verification.
  • Wire size: 0.5 – 25 mm² · Tightening torque: 2.0 N·m.
  • RoHS 2.0 compliant — environmentally responsible manufacturing.

Typical Applications

🏭 Industrial

Sub-distribution and final-circuit protection in factories and workshops.

🏢 Commercial

Offices, retail, hotels, schools, hospitals — lighting, HVAC and socket circuits.

🏬 High-Rise

Riser distribution boards in tall buildings where higher fault levels demand 10kA.

🏠 Residential

Consumer units and apartment distribution boards demanding certified safety.

Product Model Designation

GYM9 H
Product model (MCB) H = 10,000 A breaking capacity (None = 6,000 A)

Competitive Comparison vs. Tier-1 Brand 10kA MCB

The following side-by-side compares GYM9H-10kA with a representative tier-1 European-brand 10kA MCB (Schneider Acti9 iC65H) on the key selection parameters. GYM9H matches the competitor on the metrics that drive day-to-day reliability, with a clear advantage on price-to-performance.

Parameter GYM9H-10kA (GEYA) Top-tier brand MCB (reference)
Standards IEC/EN 60898-1, GB/T 10963.1 IEC/EN 60898-1, IEC/EN 60947-2
Poles 1P / 2P / 3P / 4P 1P / 2P / 3P / 4P
Rated Current (In) 1 – 63 A 1 – 80 A
Rated Voltage (Ue) 230/400V (240/415V) 230/400V
Icn (IEC 60898-1) 10 kA 10 kA
Tripping Curves B / C / D B / C / D (+MA)
Mechanical Life 20,000 ops 20,000 ops
Electrical Life 10,000 ops 10,000 ops
Uimp 4 kV 6 kV
Protection Class IP20 IP20
Module Width 18 mm / pole 18 mm / pole
Price Positioning ★ Highly economical Premium

Conclusion: GYM9H-10kA is functionally equivalent to the reference tier-1 product on breaking capacity, endurance, pole configurations, IP rating and module footprint. The tier-1 product offers a slightly higher Uimp (6 kV vs 4 kV) and a wider current range up to 80 A; for the vast majority of 1–63 A installation circuits, GYM9H delivers identical certified protection at a materially lower cost.

Outline Overall And Installing Dimensions:

GYM9H-10kA MCB product dementions

Outline & Installation Dimensions

Dimension 1P 2P 3P 4P
Width (mm) 18 36 54 72
Height (mm) 86.5 ± 0.3 (mounted on TH35-7.5 DIN rail)
Depth (mm) 80 (overall) / 50 (front protrusion)
DIN-rail Slot (mm) 45

Technical Parameters & Specifications

Parameter Specification
Model GYM9H-10kA
Product Type AC Miniature Circuit Breaker (MCB)
Standards IEC/EN 60898-1, GB/T 10963.1
Certifications CE · CB · SAA
Rated Current (In) 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 A
Rated Voltage (Ue) 1P: 240/415V~ ; 230/400V~
Rated Insulation Voltage (Ui) 500 V
Rated Impulse Withstand Voltage (Uimp) 4 kV
Breaking Capacity (Icn) 10 kA (6 kA / 10 kA available)
Operating Frequency 50 / 60 Hz
Tripping Curves B (3–5 × In) · C (5–10 × In) · D (10–14 × In)
Number of Poles 1P / 2P / 3P / 4P
Mechanical Life 20,000 operations
Electrical Life 10,000 operations
Tightening Moment 2.0 N·m
Wire Size 0.5 – 25 mm²
Protection Class IP20
Mounting TH35-7.5 DIN rail
Module Width 18 mm per pole
Connection Dual busbar connection
Indicators Transparent ID window · Contact position indicator
Environmental RoHS 2.0 compliant

Temperature Compensation

When the ambient temperature is not the baseline of 30 °C, multiply the rated current (In) by the correction factor below to obtain the effective continuous current.

Ambient Temp. -20°C -10°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C
Correction Factor 1.25 1.20 1.15 1.10 1.05 1.00 0.95 0.90 0.85

Tripping Curves (B / C / D)

GYM9H-10kA is available with three magnetic tripping characteristics so the breaker can be matched precisely to the connected load:

Curve Magnetic Trip Range Typical Application
B 3 – 5 × In Resistive loads, long cable runs, lighting and socket circuits
C 5 – 10 × In General-purpose: small motors, HVAC, mixed inductive loads (most common)
D 10 – 14 × In High inrush loads: transformers, large motors, capacitor banks

X-axis: multiples of rated current (×In).   Y-axis: tripping time in seconds. Refer to the B/C/D curve diagrams in the product gallery.

Frequently Asked Questions

Q1. What is the GYM9H-10kA?

The GYM9H is a reliable and flexible device that protects electrical systems in various settings, such as homes, offices, tall buildings, and factories. It has a strong 10kA breaking capacity and offers B, C, D tripping curves to handle heavy machinery and high-current loads safely.[[1]](https://www.geya.net/product/gym9h-10ka-1-4-pole-miniature-circuit-breaker/) Within the GYM9 family, the “H” suffix denotes the high-breaking-capacity variant — 10,000 A (10 kA) rated short-circuit breaking capacity per IEC/EN 60898-1, versus 6 kA for the standard GYM9. It comes in 1P/2P/3P/4P configurations from 1 A to 63 A and mounts on a 35 mm DIN rail at 18 mm per pole.

Q2. What functions does it provide?

  • Overload protection — thermal-bimetal element trips on sustained overcurrent.
  • Short-circuit protection — instantaneous electromagnetic trip per B/C/D curve, up to 10 kA fault current.
  • Circuit isolation — full disconnection of the protected circuit for safe maintenance.
  • Manual switching — suitable for infrequent on/off operations of the circuit.
  • Status indication — transparent ID window and contact-position indicator.
  • Expandable functions via auxiliary contacts (AX), alarm contacts (AL), shunt trip (MX), under-voltage release (MN) and motorized / remote operating mechanisms.

Q3. Which key parameters drive model selection?

  1. Rated current (In) — match to the continuous load current, adjusted by the temperature-compensation factor.
  2. Number of poles — 1P for single-phase line, 2P for L+N, 3P/4P for three-phase systems.
  3. Rated voltage (Ue) — confirm the system voltage is within 240/415V AC range.
  4. Prospective short-circuit current — must be lower than the 10 kA breaking capacity at the point of installation.
  5. Tripping curve (B / C / D) — match to load inrush characteristics.
  6. Ambient temperature — apply the correction factor (1.25 at -20 °C → 0.85 at 60 °C).
  7. Accessory requirements — auxiliary / alarm / shunt-trip / UVR / motor operator.

Q4. What configuration options are currently available?

  • Poles: 1P, 2P, 3P, 4P
  • Rated current: 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 A
  • Tripping curves: B, C, D
  • Breaking capacity: 10 kA (this model) — Basic 6 kA “GYM9” version is also offered for lower fault-level installations
  • Accessories: auxiliary contact (AX), alarm contact (AL), shunt trip (MX), under-voltage release (MN), motorized / remote operating mechanism

Contact us with your required In × poles × curve × accessory combination for a quotation.

Q5. Which standards does it meet, and which markets is it designed for?

GEYA GYM9H-10kA is designed and tested to IEC/EN 60898-1 and GB/T 10963.1, is RoHS 2.0 compliant, and carries CE / CB / SAA certifications. It targets:

  • European, Asia-Pacific, Middle East, African and Latin-American markets that specify IEC/EN-compliant MCBs;
  • Australian / New Zealand projects requiring SAA approval;
  • OEM/ODM panel builders making distribution boards, consumer units and industrial control panels;
  • Cost-sensitive projects needing a certified 10 kA MCB that performs on par with tier-1 brands at a far more economical price point.

Q6. What installation precautions should I follow?

  1. Mounting: Install vertically on a 35 mm DIN rail (TH35-7.5) inside a dry, dust-protected enclosure. The breaker itself is IP20 — the enclosure must provide the final ingress protection.
  2. Wiring direction: Connect the supply to the top terminals; observe phase / N markings on multi-pole versions.
  3. Spacing & ventilation: Provide adequate clearance between adjacent breakers and from heat sources; apply the temperature-compensation factor when ambient exceeds 30 °C.
  4. Tightening torque: Tighten terminal screws to 2.0 N·m using a wire size within 0.5 – 25 mm². No bare wire whiskers outside the terminal.
  5. Pre-energizing check: Verify continuity, insulation resistance and correct ON/OFF indication via the contact-position window before commissioning.
  6. Periodic maintenance: Operate the breaker manually from time to time to confirm mechanical operation; replace if it has interrupted a fault close to its 10 kA rating.
  7. Do not exceed ratings: Never apply DC voltage to this AC MCB — use the GYM9H-DC version for DC circuits.
Contact Us
Contact Us

Check Out The Full Catalog

Quick Info Exchange Helps Us Serve You Better
(Low-voltage and solar energy electrical components catalog)

Electrical Equipment catalog