Description
AU9-AL9
Model | AU9 | AL9 |
Type | Auxiliary Contact | Alarm Contact |
Standard | IEC/EN 60947-5-1 | IEC/EN 60947-5-1 |
Function |
||
Indicating the On/off state of
Circuit breaker |
Sending signal at the time of fault tripping of Circuit breaker | |
On the front panel, there is mechanical indication which can indicate fault tripping | ||
Application |
||
Distant indication of
Circuit breaker state |
Sending signal at the time of fault tripping | |
Voltage Ue | AC 230/400V | AC 230/400V |
DC 120V | DC 120V | |
Rated frequency | 50/60Hz | 50/60Hz |
Red Mechanica indication | No | yes |
Test function | No | yes |
Working Current | ||
230V AC 6A | 230V AC 6A | |
400V AC 3A | 400V AC 3A | |
120V DC 1A | 120V DC 1A | |
Contact Number | 1NO/NC | 1NO/NC |
Working temperature | -35~+70℃ | -35~+70℃ |
Wiring Diagram |
SH9-UV9-OV9
Model | SH8 | UV9 | OV9 | UV9+OV9
|
Type | Shunt Release | Undervoltage tripping | Overvoltage trip | Unde&Over-voltage of Single-phase
|
Standard | IEC/EN 60947-5-1 | IEC/EN 60947-1
|
IEC/EN 60947-1
|
IEC/EN 60947-1
|
Function |
||||
When it gets signal, it triggers the circuit breaker to trip. | When power voltage lowers( 35%~70%Un), it makes circuit breaker trip; When power is not supplied normally, it prevents circuit breaker from reconnecting to the circuit.
|
Monitor voltage between phase line and neutral line. When voltage rises( for example, neutral line is broken) , it triggers circuit breaker to trip. | It has function of over-voltage release, and function of making circuit breaker trip when power voltage lowers. | |
0.2 S time delay prevents the temporary lowering of voltage from causing mistrip. | rated tripping voltage range: 280vac±5%. | Rated tripping voltage range: 280vac±5%.
Rated under-voltage tripping range: 55~160v. |
||
Application |
||||
Distant control can achieve emergency breaking. | Prevent machine from restarting without control signal, ensuring safety. | Prevent over-voltage from damaging circuit and equipment. | Prevent over-voltage and under-voltage from damaging circuit and equipment. | |
Voltage Ue | AC 230/400V
AC 48V AC 12/24V |
AC 230/400V
|
AC 230/400V
|
AC 230/400V
|
DC 120V
DC 48V DC 12/24V |
||||
Rated frequency | 50/60Hz | 50/60Hz | ||
Test function | No | yes | yes | yes |
Working temperature | -25~+70℃ | -25~+70℃ | ||
Wiring Diagram
|