GYM10 Visible Miniature Circuit Breaker

  • Wide Range — 1A to 63A in 1P, 1P+N, 2P, 3P and 4P versions.
  • Breaking Capacity — 3kA, 4.5kA or 6kA to IEC/EN 60898-1 Standard.
  • Status Visible — Contact position indicator plus transparent identification window.
  • C65 Footprint — 18mm per pole, fits standard 35mm DIN rail.
  • Certified — CCC, CE INMETRO and CB certificates; 0.5-25mm² terminals.

Description

Overview

The GEYA GYM10 is a DIN-rail miniature circuit breaker (MCB) rated 1A to 63A in 1P, 2P, 3P and 4P versions, with 3kA, 4.5kA or 6kA short-circuit breaking capacity and B, C or D tripping curves according to IEC/EN 60898-1 and GB/T 10963.1. It protects final circuits against overload and short circuit at 240/415V AC, 50/60Hz, and can also be used for infrequent manual switching of a line. A transparent identification window and a contact position indicator let the installer read the actual switching state of the device, which is useful during commissioning and fault finding in a crowded distribution board.

Working Principle

The GYM10 uses a thermal-magnetic release, the same proven arrangement used across modular MCBs:

  • Thermal release — a bimetal strip heats up under sustained overload and trips the mechanism with an inverse time delay, so short starting peaks are tolerated.
  • Magnetic release — on a short circuit the solenoid trips the latch within milliseconds.
  • Arc control — the arc is driven into the arc chamber, split, cooled and extinguished, then the gases are vented.
  • Curve selection — B trips at roughly 3-5 In, C at 5-10 In, D at 10-20 In, matching resistive, mixed and high-inrush loads respectively.

Key Features

  • Contact position indication — the indicator reports the position of the contacts, not only the handle position.
  • Transparent identification function — a clear window for circuit labelling, so the board stays readable after handover.
  • Busbar flexibility — double busbar as standard, single busbar wiring available as an option.
  • C65-format module — 18mm per pole (1P 18mm / 2P 36mm / 3P 54mm / 4P 72mm), so it drops into existing enclosure layouts and cover cut-outs without redesign.
  • Cage-clamp terminals — accept 0.5mm² to 25mm² conductors, tightening torque 2.0N·m.
  • Accessory-ready — can be fitted with auxiliary devices including over/under-voltage protection units and a remote motor operator.
  • Material compliance — RoHS 2.0.

Protection and Electrical Data

  • Overload and short circuit — 3000A, 4500A or 6000A rated short-circuit capacity, selected by application and prospective fault level.
  • Isolation — provides electrical separation of the circuit in the open position, as required by IEC/EN 60898-1.
  • Insulation — rated insulation voltage 500V, rated impulse withstand voltage 4kV.
  • Endurance — 20,000 mechanical operations and 10,000 electrical operations.
  • Enclosure — IP20 degree of protection, intended for installation inside a distribution board.

Installation Notes

  • Mounting — clips onto a standard 35mm DIN rail; the clip releases for tool-free removal, so a device can be swapped without dismantling the row.
  • Termination — strip the conductor to the marked length, seat it fully in the cage clamp and tighten to 2.0N·m. Re-check terminals after the first load cycles.
  • Ambient derating — the ratings are referred to 30°C. Above that, apply the correction factors in the Technical Parameters tab; a fully loaded, densely packed board is the usual reason for nuisance tripping in summer.
  • Service — the breaker is a sealed, maintenance-free device. Do not open the housing or adjust the release.

Applications

Final circuit and sub-distribution protection in:

  • Residential distribution boards and apartment blocks
  • Commercial buildings, offices, retail and hotels
  • Light industry, machine tools, precision casting and automotive plants
  • Rail, marine, energy and power utility auxiliary circuits
  • OEM control panels and modular assemblies built to a C65 layout

Certification and Support

The GYM10 series holds CCC (3C), CE and CB certificates, and is certified for the Brazilian market. Full curves, dimensional drawings and accessory data are available in the technical manual on request.

Need help matching a rating, curve and breaking capacity to your circuit? Send your load list and prospective fault current through the Contact Us form and our engineering team will come back with a selection proposal.

GYM10 Wiring Diagram

Technical Parameters

Item Specification
Model GYM10
Standard IEC/EN 60898-1, GB/T 10963.1, RoHS 2.0
Rated current (In) 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63A
Rated voltage (Ue) 240/415V AC; 230/400V AC
Rated frequency 50/60Hz
Rated short-circuit capacity 3000A / 4500A / 6000A
Tripping curve B, C, D
Number of poles 1P, 2P, 3P, 4P (3P+N)
Rated insulation voltage (Ui) 500V
Rated impulse withstand voltage (Uimp) 4kV
Mechanical life 20,000 operations
Electrical life 10,000 operations
Terminal capacity 0.5-25mm², cage clamp terminal
Tightening torque 2.0N·m
Degree of protection IP20
Internal structure C65 modular structure, 35mm DIN rail mounting
Wiring option Suffix T: single busbar / Suffix H: double busbar
Certification CCC (3C), CE, CB, Brazil market certification

Overall and Mounting Dimensions

Poles Width (mm) Height (mm) Depth (mm)
1P 18 86.5 ±0.2 80
2P 36
3P 54
4P (3P+N) 72

Temperature Correction Factors

Ratings are referred to a baseline ambient temperature of 30°C. For other ambient temperatures, multiply In by the factor below.

Ambient temperature -20°C -10°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C
Current correction factor 1.25 1.20 1.15 1.10 1.05 1.00 0.95 0.90 0.85

Click here to download the GYM10 CE Certification
Click Here to Download the GYM10-6KA INMETRO Certification

INMETRO: The GYM10 Series MCB has passed INMETRO’s rigorous testing. This certification guarantees that our GYM10 MCB complies with the safety and performance regulations of the Brazilian market, providing customers with reliable and safe MCB products.

1. What is the GYM10 miniature circuit breaker?

The GYM10 is a modular DIN-rail miniature circuit breaker (MCB) built on a C65 internal structure, rated 1-63A at 240/415V AC, 50/60Hz, in 1P, 2P, 3P and 4P versions. It is designed to IEC/EN 60898-1 and GB/T 10963.1 for final circuits in residential, commercial and light industrial installations.

2. What are its core functions?

  • Overload protection — thermal bimetal release with inverse time characteristic.
  • Short-circuit protection — magnetic release, breaking capacity 3kA / 4.5kA / 6kA.
  • Isolation — electrical separation of the circuit in the OFF position.
  • Status reading — contact position indicator and transparent identification window.
  • Manual switching — suitable for infrequent line switching operations.

3. Which parameters decide the correct selection?

  • Rated current In — must sit between the cable capacity and the load current.
  • Tripping curve — B for resistive circuits, C for mixed and general purpose, D for transformers and motors with high inrush.
  • Breaking capacity — must equal or exceed the prospective short-circuit current at the point of installation: 3000A / 4500A / 6000A.
  • Number of poles — 1P and 2P for single phase, 3P and 4P for three-phase circuits.
  • Ambient temperature — apply the correction factor, for example 0.90 at 50°C.
  • Conductor size — terminals accept 0.5-25mm².

4. What versions and options are available?

  • Breaking capacity versions — GYM10-3kA, GYM10-4.5kA, GYM10-6kA; overload and short-circuit protection performance is consistent across the three.
  • Poles and widths — 1P 18mm, 2P 36mm, 3P 54mm, 4P 72mm.
  • Wiring option — suffix T for single busbar, suffix H for double busbar.
  • Accessories — auxiliary units including over/under-voltage protection and a remote motor operator.
  • DC version — GYM10DC to IEC 60947-2, with a dedicated arc-quenching system for telecom power supplies, battery banks and DC switchgear circuits.

5. Which standards does it meet, and which markets does it serve?

  • Standards — IEC/EN 60898-1 and GB/T 10963.1 for the AC range; IEC 60947-2 for the DC range.
  • Certificates — CCC (3C) for China, CE for the EU, CB report for multi-country recognition, plus certification for the Brazilian market.
  • Material compliance — RoHS 2.0.
  • Typical markets — projects and distribution channels in Europe, South America, the Middle East, Southeast Asia and Africa.

6. What should I watch during installation and maintenance?

  • Qualified personnel only — isolate and verify the supply before any work.
  • Torque — tighten terminals to 2.0N·m; loose terminals are the most common cause of overheating.
  • Mounting — standard 35mm DIN rail, inside an enclosure, since the device is rated IP20.
  • Heat management — leave ventilation space in fully loaded boards and derate per the temperature table.
  • Periodic check — operate the handle occasionally to keep the mechanism free, and inspect terminals for discolouration.
  • No field repair — the breaker is sealed and maintenance-free; replace it after a severe short-circuit interruption rather than opening the case.