Description
Product Highlight:
- Flexible Wiring Options: Single or double busbar configurations simplify installation and maintenance, adapting to various electrical setups.
- Transparent Identification: A clear window on the main panel shows the breaker’s status, enhancing operational efficiency.
- Contact Position Indication: Visibly indicates whether the breaker is ON or OFF, improving safety during maintenance.
- High Durability: With a mechanical life of 20,000 operations and an electrical life of 6,000, the GYM10 reduces replacement costs.
- Temperature Compensation: Ensures consistent performance across a wide temperature range (-20°C to 60°C), ideal for diverse environments.
- C65 Technology Platform: Supports DC system applications, expanding its usability in specialized scenarios.
- Modular Design: Allows integration of auxiliary contacts, alarm contacts, and other modules for customized protection.
- High-Performance Materials: Uses enhanced flame-retardant nylon and silver contacts to withstand high temperatures and ensure reliability.
- Free Tripping Mechanism: Ensures the breaker remains in a stable ON or OFF state, even during faults, enhancing safety.
- Ergonomic Handle: Large, anti-slip handle design facilitates safe and easy operation, even in demanding conditions.
Applications:
The GEYA GYM10 Miniature Circuit Breaker is versatile and suitable for a wide range of applications:
- Residential Buildings: Protects household circuits from overloads and short circuits, ensuring safety for appliances and wiring.
- Commercial Spaces: Safeguards electrical systems in offices, retail stores, and other commercial establishments.
- Industrial Environments: Provides reliable protection in factories, warehouses, and manufacturing plants with high electrical demands.
- High-Rise Buildings: Manages complex electrical distribution in multi-story structures, ensuring consistent performance.
GYM10 Miniature Circuit Breaker Technical Specification:
| Rated Current(In) | 1、2、3、4、6、10、16、20、25、32、40、50、63A |
| Rated Voltage(Ue) | 1P:230V/400V~;2P-4P:400V of 1P:240/415V~;2P~4P:415V |
| Working Frequency | 50/60Hz |
| Tripping Curves | B、C、D |
| Breaking Capacity | 3000A、4500A、6000A |
| Poles | 1P、2P、3P、4P |
| Mechanical Life | 20000 times |
| Electrical Life | 6000 times |
Temperature Compensation:
When the ambient temperature is not the baseline temperature of 30℃,the reference correction coefficient is as follows:
| Ambient Temperature | -20℃ | -10℃ | 0℃ | 10℃ | 20℃ | 30℃ | 40℃ | 50℃ | 60℃ |
| Current Correction Factor | 1.25 | 1.2 | 1.15 | 1.10 | 1.05 | 1.00 | 0.95 | 0.90 | 0.85 |