GYL9-AC-S 16–100 A Type AC-S Time-Delay RCCB

  • Detection type – Type AC detection for sinusoidal AC residual currents.
  • Timing characteristic – Catalogue Type S time-delay operating bands for coordination assessment.
  • Rated current options – 16, 20, 25, 32, 40, 50, 63, 80 and 100 A.
  • Residual current and poles – 30, 100 or 300 mA; 1P+N or 3P+N.
  • Protection boundary – This RCCB requires separate overload and short-circuit protection.
SKU GYL9-AC-S Category

Description

GYL9-AC-S Type AC-S Time-Delay RCCB

The GYL9-AC-S combines Type AC residual-current detection with the catalogue Type S operating-time bands. It is intended for sinusoidal AC residual currents. Use the complete timing table when evaluating coordination; the time-delay characteristic alone does not guarantee selectivity.

Residual-Current Detection

The Type AC characteristic is intended for sinusoidal AC residual currents. If connected equipment can produce pulsating DC or other residual-current components, select a residual-current type that matches those waveforms.

Type S Operating-Time Characteristic

The operating time changes with the applied residual current. The catalogue specifies separate Type S ranges at IΔn, 2IΔn, 5IΔn, 5–200 A and 500 A; use the complete table when assessing system coordination.

Ratings and Configuration

  • Rated current – 16, 20, 25, 32, 40, 50, 63, 80 and 100 A.
  • Rated residual operating current – 30, 100 and 300 mA.
  • Voltage and poles – 230/240 V or 400/415 V; 1P+N or 3P+N.

These values are catalogue options and do not establish that every combination is available. Confirm the complete ordering matrix for the required configuration.

Installation and Protection Boundary

  • Installation – TH35-7.5 DIN-rail mounting, IP20, 2.5 N·m tightening torque and 1–35 mm² conductor capacity.
  • Connection and indication – Dual-busbar wiring and residual-current fault indication.
  • Service life – 10,000 mechanical and 4,000 electrical operations.

The GYL9-AC-S is an RCCB and does not provide overload or short-circuit protection. Select and coordinate suitable protective devices separately for the installation.

Reference Standards and Catalogue

The GYL9 catalogue lists IEC/EN 61008-1 and GB/T 16916.1 as reference standards. Review the GYL9 catalogue and confirm the complete ordering matrix with GEYA.

Technical Parameters

Electrical Ratings

Parameter Catalogue value
Product type Type AC-S time-delay RCCB
Residual-current action type AC-S with Type S operating-time bands
Residual-current detection Sinusoidal AC
Reference standards IEC/EN 61008-1; GB/T 16916.1
Rated voltage (Un) 230/240 V; 400/415 V
Rated current (In) 16, 20, 25, 32, 40, 50, 63, 80, 100 A
Rated residual operating current (IΔn) 30, 100, 300 mA
Poles 1P+N; 3P+N
Frequency 50/60 Hz
Rated insulation voltage (Ui) 500 V
Rated impulse withstand voltage (Uimp) 4 kV
Rated conditional short-circuit current (Inc) 6 kA; 10 kA
Rated conditional residual short-circuit current (IΔc) 6 kA; 10 kA
Rated making and breaking capacity (Im) 500 A for In ≤ 50 A; 10 × In for In = 63 A
Rated residual making and breaking capacity (IΔm) 500 A for In ≤ 50 A; 10 × In for In = 63 A

Installation and Service Data

Parameter Catalogue value
Terminal tightening torque 2.5 N·m
Conductor capacity 1–35 mm²
Degree of protection IP20
Mounting TH35-7.5 DIN rail
Connection feature Dual-busbar wiring
Fault indication Residual-current fault indication
Mechanical life 10,000 operations
Electrical life 4,000 operations

Type S Operating-Time Bands

Rated current Rated residual operating current At IΔn At 2IΔn At 5IΔn At 5–200 A At 500 A
16, 20, 25, 32, 40, 50, 63, 80, 100 A 30, 100, 300 mA 0.15–0.50 s 0.06–0.20 s 0.05–0.15 s 0.04–0.15 s 0.04–0.15 s

The values above are catalogue options. Confirm the complete ordering matrix, selected configuration and system coordination before installation.

FAQs

Which residual-current waveform can the GYL9-AC-S detect?

As a Type AC RCCB, it is intended for sinusoidal AC residual currents.

What does S mean on the GYL9-AC-S?

S identifies the catalogue time-delay operating bands listed for this model. Use the complete timing table when evaluating coordination.

What are the published Type S operating-time bands?

The catalogue lists 0.15–0.50 s at IΔn, 0.06–0.20 s at 2IΔn, 0.05–0.15 s at 5IΔn, and 0.04–0.15 s at 5–200 A and 500 A.

Does the GYL9-AC-S automatically guarantee selectivity?

No. Selectivity depends on the complete system design, device ratings, residual-current settings and time-current coordination.

Which ratings are listed for the GYL9-AC-S?

Catalogue options include 16, 20, 25, 32, 40, 50, 63, 80 and 100 A; 30, 100 and 300 mA; and 1P+N or 3P+N. Confirm the complete ordering matrix for the required combination.

Does the GYL9-AC-S provide overload or short-circuit protection?

No. It is an RCCB; suitable overload and short-circuit protection must be selected separately.