GYL9-A 1P+N 3P+N Type A RCCB

  • Type A detection – Detects sinusoidal AC and pulsating DC residual currents.
  • Rated current options – 16, 20, 25, 32, 40, 50, 63, 80 and 100 A.
  • Residual-current options – 30, 100 and 300 mA.
  • Voltage and poles – 230/240 V or 400/415 V; 1P+N or 3P+N.
  • Protection scope – RCCB residual-current protection; coordinate separate overload and short-circuit protection.

GYL9-A Type A RCD Certificates

SKU GYL9-A Category

Description

GYL9-A Type A RCCB

The GEYA GYL9-A Type A RCCB detects sinusoidal AC and pulsating DC residual currents in low-voltage distribution circuits. Catalogue-listed ratings include 16, 20, 25, 32, 40, 50, 63, 80 and 100 A, rated residual operating currents of 30, 100 and 300 mA, and 1P+N or 3P+N configurations. Available combinations depend on the selected order configuration.

Residual-Current Protection

Type A detection covers the residual-current waveforms specified for circuits with sinusoidal AC and pulsating DC components. The GYL9-A is an RCCB, so overload and short-circuit protection must be selected and coordinated separately.

  • Detection coverage – Sinusoidal AC and pulsating DC residual currents.
  • Protection boundary – Residual-current protection only; this RCCB does not replace overcurrent protection.

Ratings and Configuration

Select the rated current, rated residual operating current, voltage and pole arrangement for the circuit design. Available combinations depend on the selected order configuration.

  • Electrical options – 16, 20, 25, 32, 40, 50, 63, 80 or 100 A; 30, 100 or 300 mA; 50/60 Hz.
  • System options – 230/240 V or 400/415 V with 1P+N or 3P+N poles.

Installation and Service Data

The selected configuration installs on a TH35-7.5 DIN rail. Catalogue-listed features include a dual-busbar wiring arrangement and residual-current fault indication.

  • Conductor capacity – 1–35 mm² with a specified terminal tightening torque of 2.5 N·m.
  • Mounting and protection – TH35-7.5 DIN rail and IP20.
  • Service life – 10,000 mechanical operations and 4,000 electrical operations.

Applications and Selection

Typical selection contexts include residential, commercial and industrial low-voltage distribution boards where the protection design specifies Type A residual-current detection. Confirm the expected residual-current waveform, system voltage, rated current, sensitivity, pole arrangement and applicable project requirements before selection.

Standards and Catalogue

The GYL9 catalogue references IEC/EN 61008-1 and GB/T 16916.1. Review the GYL9 catalogue and confirm the required order configuration before purchase.

Technical Parameters

The values below are GYL9 catalogue options. Available combinations depend on the selected GYL9-A order configuration.

Electrical Ratings and Selection

Parameter Specification
Product type Type A RCCB
Residual-current detection Sinusoidal AC and pulsating DC
Operating principle Electromagnetic or electronic versions; confirm the selected configuration
Rated voltage (Un) 230/240 V; 400/415 V
Rated current (In) 16, 20, 25, 32, 40, 50, 63, 80, 100 A
Rated residual operating current (IΔn) 30, 100, 300 mA
Poles 1P+N; 3P+N
Frequency 50/60 Hz
Reference standards IEC/EN 61008-1; GB/T 16916.1

Installation and Service Data

Parameter Specification
Rated insulation voltage (Ui) 500 V
Rated impulse withstand voltage (Uimp) 4 kV
Rated conditional short-circuit current (Inc) 6 kA; 10 kA
Rated conditional residual short-circuit current (IΔc) 6 kA; 10 kA
Making and breaking capacity (Im / IΔm) 500 A for In ≤ 50 A; 10 × In for In = 63 A. Confirm other ratings before ordering.
Terminal tightening torque 2.5 N·m
Conductor capacity 1–35 mm²
Degree of protection IP20
Mounting TH35-7.5 DIN rail
Mechanical / electrical life 10,000 / 4,000 operations
Connection Dual-busbar wiring arrangement
Indication Residual-current fault indication

Residual-Current Operating Time

Tripping type Rated current IΔn At IΔn At 2IΔn At 5IΔn 5–200 A 500 A
General type 16, 20, 25, 32, 40, 50, 63, 80, 100 A 30 / 100 / 300 mA ≤ 0.10 s ≤ 0.08 s ≤ 0.04 s ≤ 0.04 s ≤ 0.04 s

Operating-time values are catalogue data for the general tripping type. Confirm the selected GYL9-A configuration and applicable installation requirements before use.

FAQs

What does the GYL9-A detect?

The GYL9-A is a Type A RCCB that detects sinusoidal AC and pulsating DC residual currents.

Which ratings are available?

Catalogue options include 16, 20, 25, 32, 40, 50, 63, 80 and 100 A, with rated residual operating currents of 30, 100 and 300 mA. Confirm the required combination before ordering.

Which pole options are available?

The GYL9-A is listed with 1P+N and 3P+N configurations for 230/240 V or 400/415 V systems. Match the pole arrangement and rated voltage to the circuit design.

Does it provide overcurrent protection?

No. The GYL9-A is an RCCB for residual-current protection. Coordinate it with suitable overload and short-circuit protection according to the circuit design and installation requirements.

How is the GYL9-A installed?

Install the selected configuration on a TH35-7.5 DIN rail, use conductors within the 1–35 mm² catalogue range, and tighten the terminals to 2.5 N·m.

Can the GYL9-A be used for EV charging equipment?

The GYL9-A detects sinusoidal AC and pulsating DC residual currents. Where the EV charging equipment requires dedicated 6 mA smooth DC residual-current detection, specify the GYL9-EV and confirm the complete protection arrangement for the charging equipment. Do not treat the GYL9-A or the standard GYL9-B as an equivalent substitute for that dedicated requirement.