Description
Features
- Indication function of contact position
- Transparent cover designed to carry label.
- Support 35mm Din – rail installation
- Support top incoming and bottom outgoing wiring type, or bottom incoming and top outgoing wiring type.
- Able to select electrical accessories and achieve distant indication of MCB condition: breaking, closed, and fault tripping.
- Able to select electrical accessories and realize under-voltage and over-voltage protection of MCB and distant shunt release.
Rated current In | 32A、63A、100 A、125A |
Poles | 1P 2P 3P 4P |
Rated voltage Ue | 1P: 230/400V~ ; 2/3/4P:400V~ |
Insulation voltage Ui | 500V |
Rated frequency | 50/60Hz |
Rated short-time withstand current lcw | 12le 1s |
Rated making and breaking capacity | 3le, 1.05Ue, cosφ=0.65 |
Rated short circuit making capacity | 20le, t=0.1s |
Using the categories | AC-22A |
Rated impulse withstand voltage(1.2/50)Uimp | 6000V |
Dielectric test voltage at and ind.Freq.for 1min | 2.5kv |
Electrical life | 1500 |
Mechanical life | 8500 |
Protection degree | IP20 |
Installation | |
Ambient temperature (with daily average ≤35℃) | -5~+40℃ |
Storage temperature | -25~+70℃ |
Terminal Connection type | Cable/Busbar |
Terminal size top/bottom for cable | 50mm² 18-1/0 |
Tightening torque | 3.5N*m 22 |
Connection | Top and bottom |
Reviews
There are no reviews yet.