GYCM8EY3 Molded Case Circuit Breaker (MCCB)

  • Core Application: Specifically engineered for 3-phase power supply lines without a neutral wire (local grounding), making it highly compatible with American standard power supply systems.
  • High Capacity: Rated insulation voltage of 1000V, rated operating voltage up to AC400V, and frame current up to 800A.
  • Intelligent Protection: Electronic overcurrent striker providing overload, short-circuit, over/under-voltage, phase-loss, and PV anti-islanding protection.
  • Smart Monitoring: Built-in LCD display with real-time measurement of current, voltage, frequency, and 3-phase imbalance.
  • Remote Capabilities: Supports RS-485 communication (Modbus-RTU / DL/T 645-2007) for telemetry, telemessage, remote control, and remote adjustment.

→ Download GEYA CYCM8EY3 MCCB Catalog

 

SKU GYCM8EY3 Category

Description

Product Overview

GYCM8EY3 Intelligent Molded Case Circuit Breaker (MCCB) delivers advanced protection for 3-phase power distribution networks up to 800A. Featuring an electronic controller, RS-485 communication, and specialized support for systems without a neutral wire, it ensures reliable operation for industrial and commercial applications. As a professional manufacturer, GEYA has engineered this intelligent breaker to excel in infrequent line conversions and motor starting scenarios.

A standout feature of the GYCM8EY3 series is its specialized design for unique three-phase power supply lines that do not carry a neutral wire and rely on local grounding. This makes the breaker exceptionally well-suited for regions and facilities utilizing American standard power supply configurations. Equipped with a comprehensive digital interface, it allows operators to monitor real-time electrical parameters and event logs directly from the device or via an upper computer software system.

Key Features & Working Environment

  • Comprehensive Protection: Safeguards against overload, short-circuit, over-voltage, under-voltage, phase-loss, over-frequency, under-frequency, and voltage/current imbalances.
  • Photovoltaic Integration: Includes passive anti-islanding protection, making it suitable for modern renewable energy grids.
  • Event Logging: Stores up to 10 trip fault records, 30 daily max/min value records, and 10 alarm event records for precise troubleshooting.
  • Ambient Temperature: Operates reliably between -5°C and +40°C.
  • Altitude & Atmosphere: Designed for installations up to 2000 meters. Withstands relative humidity up to 50% at 40°C (higher humidity permissible at lower temperatures, e.g., 90% at 20°C).
  • Installation Category: Class III, Pollution Degree 3.

Product Dimensions

GYCM8EY product dimensions

Parameter and Specification

Model GYCM8EY3-250 GYCM8EY3-400 GYCM8EY3-630 GYCM8EY3-800
Shell Frame Rating Current (In) 50A-125A
100A-250A
160A-400A 250A-630A 630A (250A-630A)
800A (320A-800A)
Poles 3P
Rated Operating Voltage (Ue) AC400V
Rated Insulation Voltage (Ui) 1000V
Rated Impulse Withstand Voltage (Uimp) 8kV
Short Circuit Breaking Capacity Designator M | H M | H M | H M | H
Rated Operating Short-Circuit Breaking Capacity (Ics) 35kA | 65kA 50kA | 70kA 50kA | 70kA 50kA | 65kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu) 50kA | 65kA 50kA | 70kA 50kA | 70kA 50kA | 85kA
Rated Short-Time Withstand Current (Icw) 10kA/1s 10kA/1s 10kA/1s 20kA/1s
Overcurrent Striker Type Electronic

Symbol Explanation

Symbol Explanation
Imn Controller Shell Frame Current
In Rated current of controller
IR Overload long delay tripping setting current
TR Overload long delay setting time
Isd Short-circuit short-delay setting current
Tsd Short-circuit short-delay setting time
Ii Short-circuit instantaneous tripping setting current
Uvo / Tvo Overvoltage protection action value / delay value
Uvu / Tvu Undervoltage protection action value / delay value

Product Characteristics & Functions

Categorization Descriptions Availability
Display & Operation LCD display + LED indicator, Button interface ●
Measurement Function Three-phase current, Three-phase voltage, Voltage frequency, Three-phase voltage/current unbalance ●
Current Protection Overload long delay, Short-circuit short-delay, Short-circuit instantaneous, Three-phase current imbalance ●
Voltage Protection Under/over voltage, Phase loss, Three-phase voltage imbalance, Voltage under/over frequency ●
Communication Functions Modbus-RTU protocol, RS-485 hardware
(DL/T 645-2007 protocol is optional)
● / ○
Event Logging 10 trip faults, 30 days max/min records, 10 alarm events, 10 high voltage loss/restoration records ●

Note: “●” indicates the function is available; “○” indicates the function is optional.

Layout and Installation Dimensions (mm)

Dimension GYCM8EY3-250 GYCM8EY3-400 GYCM8EY3-630 GYCM8EY3-800
H 136 160 160 172
A 105 140 140 210
B 165 257 257 275.5
B1 126 194 194 243
W1 35 87 87 151
D 4*Φ4.5 4*Φ7 4*Φ7 4*Φ8

High Altitude Capacity Reduction

If the altitude exceeds the applicable working environment of 2000m, the electrical performance of the circuit breaker must be corrected according to the following table:

Altitude (m) 2000 2500 3000 3500 4000
Power frequency withstand voltage (V) 2500 2250 1950 1775 1625
Insulation withstand voltage (V) 1000 900 780 710 650
Maximum operating voltage (V) 400 350 312 284 260
Working current correction factor 1 0.98 0.95 0.92 0.90

Frequently Asked Questions (FAQs)

1. What is the GYCM8EY3 Intelligent MCCB?

The GYCM8EY3 is an intelligent molded case circuit breaker equipped with an electronic controller. It is designed to distribute power and protect circuits against severe electrical faults in networks up to 800A and 1000V insulation voltage.

2. What functions does it provide?

It provides comprehensive protection including overload, short-circuit, over/under-voltage, phase-loss, and PV anti-islanding. Additionally, it offers measurement functions (voltage, current, frequency) and 4-remote communication (telemetry, telemessage, remote-control, remote-adjustment) via RS-485.

3. What are the key parameters influencing selection?

When selecting this MCCB, consider the shell frame rating current (ranging from 50A to 800A), the short-circuit breaking capacity required by your grid (M standard or H high capacity), and your specific communication protocol needs (Modbus-RTU or DL/T 645).

4. What options are currently available?

The series is available in four main frame sizes: 250, 400, 630, and 800. Each frame size offers options for standard (M) or high (H) breaking capacities, ranging from 35kA up to 85kA ultimate breaking capacity (Icu).

5. What standards does it comply with, and which markets is it designed for?

The product strictly complies with GB/T 14048.2-2020 and GB/T 22710-2008 standards. It is designed for global industrial markets and is exceptionally well-suited for regions utilizing American standard power supply systems, particularly 3-phase lines without a neutral wire.

6. What are the installation precautions?

Ensure the installation altitude does not exceed 2000 meters and the ambient temperature remains between -5°C and +40°C. Avoid locations with strong electromagnetic interference (exceeding 5 times the geomagnetic field) and ensure correct polarity when wiring the RS-485 communication interface.

Contact Us
Contact Us

Check Out The Full Catalog

Quick Info Exchange Helps Us Serve You Better
(Low-voltage and solar energy electrical components catalog)

Electrical Equipment catalog