GRV8-4UVR Three Phase Under Voltage Relay

The GEYA GRV8-4UVR is a specialized three phase under voltage relay. It‘s compact 36mm width allows for seamless installation in space-constrained control panels, while the adjustable settings provide flexibility to tailor protection to your specific needs. Whether you’re managing a manufacturing plant, HVAC system, or power distribution network, the GRV8-4UVR delivers the precision and reliability you need.

  • Supply Voltage:AC 220V / 380V / 400V
  • Measuring Frequency Range:45Hz – 65Hz
  • Voltage Measurement Accuracy:<1%
  • Under Voltage Setting Range:Adjustable (e.g., 170V – 210V per phase)*
  • Trip Delay Time:Adjustable (e.g., 0.1s – 10s)*

→ Download GRV8-4UVR Three Phase Under Voltage Relay Catalog PDF

Category

Description

Product Highlight:

3-Phase Voltage Monitoring: Unlike single-phase relays, the GRV8-4UVR monitors all three phases simultaneously, ensuring balanced protection for systems where phase integrity is critical.

Adjustable Under Voltage Thresholds: Fine-tune the under voltage protection levels to match the specific requirements of your equipment.

Phase Imbalance and Sequence Protection: Detects and responds to phase imbalances and incorrect phase sequences, preventing motor damage and system failures.

True RMS Measurement: Ensures accurate voltage detection, even in environments with harmonics or non-linear loads.

LED Indicators: Provides clear, real-time status updates for easy monitoring and diagnostics.

Compact Design: The 36mm width and DIN rail mounting make it ideal for space-efficient installations in control panels.

Panel Diagram:

Panel Diagram

Functions Diagram:

Functions Diagram

Wiring Diagram:

Wiring Diagram

Dimensions(mm):

Dimensions

Model GRV8-4UVR Three Phase Under Voltage Relay
Function Under voltage
Monitoring terminials L1-L2-L3-N
Supply terminals L1-N
Rated supply voltage(Un) 220V/230V/240V
Rated supply frequency 45Hz-65Hz
Under voltage threshold R:fixed 75% of Un
Trip delay time(Tu) 0.1s
Hysteresis 5V
Measurement error ≤1%
Power on delay time(Td) Adjustable: 5min-15min
Recovery delay time(Tr) Adjustable: 5min-15min
Konb setting accuracy 10% of scale value
Supply indication green LED
Output indication red LED
Output 1×SPDT
Current rating 10A/AC1
Switching voltage 250VAC/24VDC
Mechanical life 1*107
Electrical life(AC1) 1*105
Operating temperature -20℃ to +55℃(-4℉ to 131℉)
Storage temperature -35℃ to +75℃(-22℉ to 158℉)
Mounting/DIN rail Din rail EN/IEC 60715
Protection degree IP40 for front panel/IP20 terminals
Operating position any
Overvoltage category III
Pollution degree 2
Max.cable size(mm²) solid wire max.1*2.5 or 2*1.5/with sleeve max.1*2.5(AWG 12)
Tightening torque 0.8Nm
Dimensions 90×18×64mm
Weight 63g,65g
Standards EN 60255-1,IEC60947-5-1