Description
Applications
GEYA pulse output time relay is used to delay and generate a pulse, which is used to delay the connection of a load for a period of time.
Function Features
-Separate delay time and pulse width settings can set different delay times.
-Time scale 0.1 s – 100 days.
-The delay time can be reset by shorting S-A1.
-With AC/DC 12V-240V ultra-wide operating voltage specifications are optional.
-Relay status is indicated by LED.
-1-MODULE, DIN rail mounting.
GRT8-P1 | GRT8-P2 | |
Function | Pulse output time relay | |
Supply terminals | A1-A2 | |
Voltage range(W240) | AC/DC 12-24V(50-60Hz) | |
Burden(W240) | AC 0.09-3VA/DC 0.05-1.7W | |
Voltage range(A230) | AC230V(50-60Hz) | |
Power input(A230) | AC max.6VA/1.3W | AC max.6VA/1.9W |
Supply voltage tolerance | -15%;+10% | |
Supply indication | green LED | |
Time ranges | 0.1s-100days | |
Time setting | potentiometer | |
Time deviation | 10%-mechanical setting | |
Repeat accuracy | 0.2%-set value stability | |
Temperature coefficient | 0.05%/℃,at=20℃(0.05%°F, at=68°F) | |
output | 1×SPDT | 2×SPDT |
Current rating | 16A(AC1) | 2x16A(AC1) |
Switching voltage | 250VAC/24VDC | |
Min. breaking capacity DC | 500mw | |
Output indication | red LED | |
Mechanical life | 1×10^7 | |
Electrical life(AC1) | 1×10^5 | |
Reset time | max.200ms | |
operating temperature | -20℃ to+55℃(-4°F to 131°F) | |
Storage temperature | -35℃to+75℃ (-22°F to 158°F) | |
Mounting/DIN rail | Din rail EN/IEC 60715 | |
Protection degree | IP40 for front panel/IP20 terminals | |
Operating position | any | |
overvoltage cathegory | Ⅲ. | |
Pollution degree | 2 | |
Max.cable size(mm²) | solid wire max.1×2.5 or 2×1.5/with sleeve max.1×2.5(AWG12) | |
Dimensions | 90×18×64mm | |
Weight | 1xSPDT:W240-62g,A230-61g | |
2xSPDT:W240-82g,A230-82g | ||
Standards | EN61812-1,IEC60947-5-1 |