GRT6-P1 AC/DC 24-240V Pulse Output Time Relay

The GEYAGRT6-P1 AC/DC 24-240V Pulse Output Time Relay is a highly adaptable pulse output time relay, offering seamless operation across a broad voltage range. Ideal for environments with fluctuating power sources, it ensures consistent performance in a compact package.

  • Power Supply: AC/DC 24V-240V
  • Contact Configuration: 1× SPDT
  • Time Range: 0.1 seconds to 100 days
  • Delay Time Adjustment: 10% to 100% adjustable
  • Pulse Width Setting: Customizable
  • Reset Function: Short S-A1 terminals
  • Indicator: LED status display
  • Mounting: DIN rail, 1-MODULE

→ Download GRT6-P1 AC 230V Pulse Output Time Relay Catalog PDF

Category

Description

Product Highlight:

  • One SPDT contact for reliable circuit control
  • Supports AC/DC 24V-240V power input
  • Separate controls for delay time and pulse duration
  • Adjustable timing from 0.1 seconds to 100 days
  • Easy delay reset by shorting S-A1
  • LED for instant relay status visibility
  • 1-MODULE size, designed for DIN rail installation

Panel Diagram:

Panel Diagram

Wiring Diagram:

Wiring Diagram

Setting Description:

Setting Description

Functions Diagram:

Functions Diagram

Dimensions(mm):

Dimensions

Model GRT6-P1
Function Pulse output time relay
Supply terminals A1-A2
Voltage range AC/DC 24-240V(50-60Hz)
Burden AC 0.7-3VA/DC 0.5-1.7W
Voltage range AC 230V(50-60Hz)
Power input AC max.6VA/1.3W
Supply voltage tolerance -15%;+10%
Supply indication green LED
Time ranges 0.1s-100days
Time setting potentionmeter
Time deviation 10%-mechanical setting
Repeat accuracy 0.2%-set value stability
Temperature coecient 0.05%/℃,at=20℃(0.05%℉,at=68℉)
Output 1×SPDT
Current rating 10A/AC1
Switching voltage 250VAC/24VDC
Min.breaking capacity DC 500mW
Output indication red LED
Mechanical life 1*107
Electrical life(AC1) 1*105
Reset time max.200ms
Operating temperature -20℃ to +55℃(-4℉ to 131℉)
Storage temperature -35℃ to +75℃(-22℉ to 158℉)
Mounting/DIN rail Din rail EN/IEC 60715
Protection degree IP40 for front panel/IP20 terminals
Operating position any
Overvoltage cathegory III.
Pollution degree 2
Max.cable size(mm²) solid wire max.1*2.5 or 2*1.5/with sleeve max.1*2.5(AWG 12)
Dimensions 90×18×64mm
Weight 1×SPDT:S240-53g,A230-65g
Standards EN 61812-1,IEC60947-5-1

 

Contact Us
Contact Us

Check Out The Full Catalog

Quick Info Exchange Helps Us Serve You Better
(Low-voltage and solar energy electrical components catalog)