Core Specifications: Supports a rated current range of 10A to 63A with 2P, 3P, and 4P options, operating at 220V/380V (50/60Hz) with Class CB overload and short-circuit protection.
Intelligent Control: Features the “Z” Intelligent Model with an LED screen for real-time status monitoring and RS485 programming capabilities for smart grid integration.
Dual Operation Modes: Offers both Automatic (detecting phase failure, under/over voltage) and Manual modes, ensuring flexibility for maintenance and emergency switching.
Advanced Safety: Built-in fire protection linkage (DC24V signal) forces dual breaking in emergencies, plus a mechanical interlock to prevent simultaneous connection of both power sources.
Robust Design: Compact structure engineered for high stability, capable of operating in temperatures from -15°C to +60°C and altitudes up to 2000m.
GATS-W8Z is a state-of-the-art Dual Power Smart Automatic Transfer Switch (ATS) designed to ensure continuous power supply in critical environments. Combining GEYA miniature circuit breaker (MCB) with a high-performance motor transmission and an intelligent controller, this device offers rapid switching with exceptional reliability. (Z means Intelligent Model, basic model details: GATS-W8)
Smart & Reliable Protection
Classified as a Class CB device, the GATS-W8Z doesn’t just switch power, it protects your circuits. It provides comprehensive protection against short circuits and overloads. The intelligent controller monitors voltage levels in real-time:
Under-voltage Protection: Triggers when phase voltage drops below AC 187V.
Over-voltage Protection: Triggers when phase voltage exceeds AC 263V.
Versatile Operation Logic
Auto Mode: Automatically switches to the reserve power source if the normal source fails or deviates from voltage standards. It features auto-recovery, switching back to the normal source once it is restored.
Manual Mode: Allows operators to control the switch via buttons or a handset, ideal for routine maintenance.
Fire Linkage: Includes a specialized DC24V port that receives fire alarm signals to force the switch into a “Double Break” (OFF) position, cutting power to prevent secondary hazards.
Application Scenarios
Designed in compliance with GB/T14048.1-1 standards, the GATS-W8Z is essential for terminal double-loop power supply systems. It is widely used in high-rise buildings, shopping malls, and industrial facilities to guarantee power for fire pumps, smoke fans, elevators, and emergency lighting.
Smart Grid, Smart Monitoring
Smart grid applications require GATS-W8Z ATS with communication capabilities to achieve “four remote” functions: remote signaling, remote measurement, remote control, and remote adjustment.
Unattended locations and urban networks require products with intelligent communication capabilities.
High-end buildings and banking/financial systems require ATSE (Automatic Telemetry, Remote Sensing, and Remote Adjustment) monitoring systems.
Product Panel Display & Operation
Parameter
Specification
Model Name
GATS-W8Z (Intelligent Model)
Rated Current (In)
10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
Poles
2-Pole, 3-Pole, 4-Pole
Rated Voltage (Ue)
AC 220V (2P) / AC 380V (3P, 4P)
Frequency
50Hz / 60Hz
ATSE Class
Class CB (with Overload & Short Circuit Protection)
Display Interface
LED Screen (Shows Working Status)
Operation Modes
Automatic, Manual
Voltage Protection
Under-voltage: <187V | Over-voltage: >263V
Fire Protection
DC 24V Signal (Triggers Dual Breaking)
Ambient Temperature
-15°C to +60°C (24h average <35°C)
Installation Altitude
≤ 2000 M
Communication
RS485 Programming Support
What is the function of the “0” dual-position?
Built on CB-class architecture and intelligent control technology, providing comprehensive power transfer protection and physical isolation solutions.
Fire Safety Linkage & Emergency Isolation
In modern building electrical design, fire safety codes mandate the disconnection of all “non-fire-related power supplies” during an emergency. Traditional ATS designs without a neutral position often require additional auxiliary contactors. The GATS-W8Z is equipped with a dedicated 24VDC fire linkage interface. Upon receiving a fire alarm signal, it can be remotely triggered and forced into a “double-break” (OFF) neutral state, instantly achieving complete physical isolation, perfectly complying with stringent fire safety standards.
When switching high currents under load, contact separation inevitably generates high-temperature electrical arcs. If traditional two-position designs are used, arcs can easily bridge the gap, leading to a catastrophic phase-to-phase short circuit. The GATS-W8Z utilizes a genuine three-position mechanical structure. Its intermediate “neutral” position serves as a critical buffer and isolation zone for mechanical movement and arc extinguishing. It ensures the arc is completely extinguished before closing the other power source.
Maintenance Safety & Physical Isolation
When performing routine maintenance within a power distribution cabinet, strict adherence to “dead-work” procedures is the absolute baseline for personal safety. The GATS-W8Z supports a manual operation mode, allowing maintenance personnel to manually shift the switch to the intermediate “double-break” position. This operation establishes a clearly visible and complete physical isolation breakpoint, effectively preventing accidental equipment activation or unexpected energization.
Intelligent Interlock & Prevent Faulty Transfers
If a short-circuit fault occurs causing the main power supply to trip, a blind automatic transfer would cause the backup power source to close directly onto the short circuit. As a high-end CB-class ATS, the GATS-W8Z features a built-in intelligent controller. Once it detects a trip caused by a downstream short circuit, the smart brain immediately executes an “electrical interlock”, terminates the automatic transfer sequence, and locks the switch in the neutral position.