Address: Wenzhou Bridge Industrial Zone

GATS-G Isolation Automatic Transfer Switch (ATS)

SKU: GATS-G Category:

Description

In compliance with GB/T14048.11

Rated operating voltage(Ue):AC440V

Rated making capacity(A Rms):10 Ie

Rated breaking capacity(A Rms):8 Ie

Rated control supply voltage:DC24V、48V、110V、AC220V

Frame class 100 250 630 1600 3200
Rated current In(A) 16 20 25 32 40 50 63 80 100 125 160 200 225 250 315 350 400 500 630 800 1000 1250 1600 2000 2500 3200
Rated insulation voltage(Ui) 690V 800V
Rated concussion withstand voltage(Uimp) 8KV
Rated working voltage(Ue) AC400V
Using category AC-33iB
Rated short-circuit connection capacity 8KA 17KA 26KA 67.5KA
Rated short-time withstand current(lcw) 5kA/30ms 10kA/60ms 12.6kA/60ms 32kA/60ms
Transfer time I-ll or ll-I 2.5s 1.2s 1.8s 2.4s
Control voltage DC24V、48V、110V,AC220V
Rated frequency Start 20W 325W 355W 400W 440W 600W
Normal 62W 74W 90W 98w 120W
Weight(kg) 4Pole 3.4 6 7.6 15.8 16.8 36 36 37 38.6 55 61 67
  1. The primary wiring diagram to see the picture.
  2. The control power is derived from normal power,emergency power cand N phases.
  3. Ⅰ and Ⅱ line control power AC220V connected with terminal 102~103,104~105respectively,102 and 104 are normal power and emergency power live line respective.
  4. Terminal 101,106 are acting as a signal lamp to control the power supply.
    Note:101 and 106 couldn’t be connected with any other lines.
  5. When above(under) input line, under(above)terminal Ⅰ and Ⅱ line A, B, C phases will be connected with copper lines or lines acting as output.