GYM9H-63-ZW 10kA DC MCB for PV Solar System

The GYM9H-63-zw DC circuit breaker is suitable for DC lines with a rated voltage up to 1200V and a rated current up to 63A. It is used for overload and short-circuit protection, and can also be used for infrequent operation and conversion of lines. It is applicable to DC system application scenarios such as communications and photovoltaics.

  • Compliant with RoHS 2.0 environmental standards
  • Built-in shorting bar connection
  • DC non-polarity
  • Contact position indication function
  • Wiring capacity: (0.5-16)mm²

Description

The GEYA GYM9H-63-zw DC MCB is specifically designed to protect DC circuits with rated voltages up to 1200V and currents up to 63A. It provides reliable protection against both overload and short circuits, and can also be used for infrequent circuit switching operations. Its high-performance design, including a 10kA breaking capacity, makes it a perfect choice for modern DC systems. This product complies with IEC/EN 60947-2 and GB/T 14048.2 standards.

Key Features

  • High Breaking Capacity:Rated for 10kA, ensuring safety in high-fault current scenarios.
  • Non-Polar Design:The circuit breaker is non-polarized, simplifying installation and wiring by eliminating the risk of incorrect polarity connections.
  • Wide Voltage Range:Supports various system architectures with options for 300VDC (1P), 600VDC (2P), 900VDC (3P), and 1200VDC (4P).
  • Contact Position Indicator:Features a visual indicator to clearly show the status of the contacts.
  • High Endurance:Built for longevity with a mechanical life of 20,000 cycles and an electrical life of 1,500 cycles.
  • Easy Installation:Mounts on a standard TH35-7.5 DIN rail.
  • RoHS Compliant:Manufactured in compliance with environmental RoHS standards.

Primary Applications

The robust design and high DC voltage rating make the GYM9H-63-zw ideal for a range of demanding applications, including:

  • Photovoltaic (PV) Solar Systems
  • Energy Storage Systems (ESS)
  • Battery Banks and UPS
  • DC Communication Systems
  • Other DC-powered equipment and circuits

Tripping Curves

GEYA GYM9H-63-zw Tripping-Curves

Temperature Compensation

Ambient Temperature (°C) Current Correction Coefficient
-20 1.25
-10 1.20
0 1.15
10 1.10
20 1.05
30 1.00
40 0.95
50 0.90
60 0.85

Tripping Characteristics

Tripping Type Current (A) Initial State Start Time Expected Result Reference Temperature
B, C, D 1.05 In Cold state t ≥ 1h (In ≤ 63) No tripping 30°C
B, C, D 1.3 In Hot state t ≤ 1h (In ≤ 63) Tripping 30°C
B, C, D 2.55 In Cold state 1s < t < 120s Tripping 30°C

GEYA GYM9H-63-zw Wiring Diagram

Technical Parameters

Rated Current (In) 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63A
Rated Voltage (Ue) 1P: 300VDC; 2P: 600VDC; 3P: 900VDC; 4P: 1200VDC
Rated Insulation Voltage (Ui) 1200V
Number of Poles 1P, 2P, 3P, 4P
Tripping Curve B, C, D
Breaking Capacity 6kA, 10kA
Mechanical Life 20,000 times
Electrical Life 1,500 times
Tightening Torque 2.0 N·m
Protection Class IP20
Mounting Method TH35-7.5 Standard DIN Rail