Power Quality Solutions / Medical & Healthcare
Power Quality Solution - Medical

Clean, Quiet, Always-On Power for Healthcare

MRI and CT systems inject harmonics while demanding rock-steady voltage, in an uptime-critical, low-noise environment. GEYA AHF and the low-noise ASVG-LN clean the waveform and hold voltage quietly enough for clinical areas.

The Problem

Power Quality in a Hospital

Healthcare facilities stress the grid in three specific ways. We measure each before recommending hardware.

Harmonics from MRI / CT Imaging

Imaging systems and their drives inject pulsed harmonic currents that distort the waveform and can disturb other sensitive medical equipment.

Fix · AHF

Strict Voltage Stability for Diagnostics

Diagnostic and life-support equipment needs voltage held within a tight band; sags or swings can corrupt imaging or interrupt critical care.

Fix · SVG / AVC

Uptime-Critical, Low-Noise Environment

Power-quality gear in or near clinical areas must run continuously and quietly - standard cabinets are often too loud for wards and imaging suites.

Fix · Silent ASVG-LN
Hospital imaging suite supported by a GEYA AHF and low-noise ASVG
The GEYA Approach

Clean Waveform, Whisper-Quiet

Imaging systems inject harmonics while demanding steady voltage. A GY-AHF cancels MRI / CT harmonics, a GY-SVG holds voltage and power factor, and the low-noise GY-ASVG-LN - down to 45 dB - does reactive, harmonic and imbalance compensation quietly enough for clinical areas. A GY-AVC keeps terminal voltage steady through dips for life-critical loads.

  • GY-AHF cancels 2nd-50th harmonics from imaging systems
  • GY-SVG holds PF ≥0.99, response <10 ms for stable diagnostics
  • GY-ASVG-LN: all-in-one compensation at just 45 dB
  • Wi-Fi / RS485 monitoring for uptime-critical facilities
THDu 17% → 3% Noise 45 dB PF → 0.99
Recommended Products

What We Deploy in Healthcare

A quick map from each hospital power-quality problem to the GEYA product that solves it.

Power Quality ProblemRecommended ProductVoltage RangeKey Spec
Imaging (MRI / CT) harmonicsAHF · GY-AHF Series220V – 800V2nd–50th, ≥95%
Voltage stability for diagnosticsSVG · GY-SVG220V – 800V<10 ms, PF ≥0.99
Low-noise / clinical-area compensationSilent · GY-ASVG-LN220/380VNoise 45 dB
Voltage dips on critical loadsAVC · GY-AVC220/380V, 30–400kVA±20%, stepless

DSP digital control (SVG: TI TMS320F28335; AHF / ASVG: TI TMS320F28377), 50/60 Hz, single- or three-phase (3-/4-wire), parallel-capable, two- & three-level. Device voltage 220–800 V; 10/35 kV via high-side sampling. Module ratings: SVG 5–150 kvar, ASVG 3–150 kvar, AHF 15–200 A, AVC 30–400 kVA.

Proof

Sensitive-Load Projects

Representative GEYA deployments on UPS-backed and harmonic-sensitive loads, with measured before/after results.

Critical Power

AHF for UPS Output Voltage Distortion

THDu 17% → 3%No downtime

Sensitive equipment harmonics pushed UPS output voltage THD to 17%, risking shutdown. A high-performance AHF cut it to about 3% on all three phases, keeping critical loads online.

Facility HVAC

AHF for Precision-Cooling Harmonics

THDi 60% → 5%PF 0.84 → 0.96

Variable-frequency precision-cooling compressors injected harmonics into the power room. A high-performance AHF cut current THD from 60% to 5% and lifted power factor from 0.84 to 0.96.

Selection Guide

Healthcare - Common Questions

Engineer-to-engineer answers to help you spec the right device for a medical facility.

How do I clean MRI / CT harmonics without adding noise?

Use the low-noise GY-ASVG-LN - it does reactive, harmonic (2nd-50th) and imbalance compensation in one cabinet at just 45 dB, quiet enough to sit near imaging suites, with a built-in grid-side sampling CT for easy installation.

Will an AHF or SVG keep diagnostic voltage stable?

Both help. A GY-AHF AHF cleans the harmonics that distort UPS and equipment voltage (a GEYA project cut UPS output THD from 17% to about 3%), while a GY-SVG holds voltage and power factor with a response under 10 ms; a GY-AVC adds series voltage regulation through dips.

Is there a silent unit for clinical areas?

Yes - the GY-ASVG-LN is purpose-built for noise-sensitive environments at 45 dB. For uptime-critical sites it pairs with Wi-Fi / RS485 monitoring so facilities teams can watch power quality 24/7.

More Solutions

Explore Other Industries

Different load, different fix. See how GEYA solves power quality across sectors.

Get Started

Powering a Hospital or Clinic?

Send us your single-line diagram and imaging / load details - our engineers will model your facility and recommend the right AHF, SVG, silent ASVG-LN or AVC solution.

Contact Us