The challenge on the rolling line
At the East China plant, AC/DC and variable-frequency rolling mills created nonlinear loads on the 380 V AC system. The project brief identifies transient impact loads as a key challenge for harmonic compensation.
The filter therefore needed fast, accurate compensation and the ability to tolerate current surges. The project also aimed to address equipment misoperation, cable overheating and transformer noise associated with harmonic current.
Why an active power filter was used
The installed APF had 600 A of total capacity. It senses harmonic load current and injects compensating current in parallel with the electrical system.
For this rolling line, filter selection had to account for changing load current and the specified tolerance for current surges. The 600 A figure is installed APF capacity, not the mill's load-current rating.
Reported THDi fell from above 30% to below 10%
The project brief reports current total harmonic distortion (THDi) above 30% before APF installation and below 10% afterward. It also reports less electrical noise and reduced busbar resonance.
| Observation | Before APF installation | After APF installation |
|---|---|---|
| Current THDi | Above 30% | Below 10% |
| Electrical noise and busbar resonance | Harsh noise; abnormal resonance | Reported to be reduced |
What to check on a similar steel mill
For a similar project, measure at the proposed APF connection point under representative rolling conditions before selecting filter capacity.
- Record voltage, current, THDi and the harmonic spectrum under representative operating conditions.
- Identify the bus or feeder where compensation is required and review the available installation space.
- Select APF capacity from the measured harmonic current, allowing for the site's operating margin.