Steel Mill Harmonic Mitigation: A 600 A APF Case Study

At a steel rolling plant, harmonic current from AC/DC and variable-frequency drives was linked to harsh electrical noise and unusual resonance sounds at the busbar. A 600 A active power filter (APF) was installed on its 380 V AC system.

Application

AC/DC and variable-frequency rolling drives

System

380 V AC

Filter

600 A total APF capacity

Reported THDi

Above 30% before; below 10% after

The challenge on the rolling line

At the East China plant, AC/DC and variable-frequency rolling mills created nonlinear loads on the 380 V AC system. The project brief identifies transient impact loads as a key challenge for harmonic compensation.

The filter therefore needed fast, accurate compensation and the ability to tolerate current surges. The project also aimed to address equipment misoperation, cable overheating and transformer noise associated with harmonic current.

Why an active power filter was used

The installed APF had 600 A of total capacity. It senses harmonic load current and injects compensating current in parallel with the electrical system.

For this rolling line, filter selection had to account for changing load current and the specified tolerance for current surges. The 600 A figure is installed APF capacity, not the mill's load-current rating.

Reported THDi fell from above 30% to below 10%

The project brief reports current total harmonic distortion (THDi) above 30% before APF installation and below 10% afterward. It also reports less electrical noise and reduced busbar resonance.

ObservationBefore APF installationAfter APF installation
Current THDiAbove 30%Below 10%
Electrical noise and busbar resonanceHarsh noise; abnormal resonanceReported to be reduced
Current panel before harmonic mitigation showing channel readings of 30.11%, 33.50%, and 30.71%
Before harmonic mitigation (project brief, Figure 1.1). Displayed readings for channels 1–3: 30.11%, 33.50%, and 30.71%.
Current panel after harmonic mitigation showing channel readings of 9.68%, 9.90%, and 8.31%
After harmonic mitigation (project brief, Figure 1.2). Displayed readings for channels 1–3: 9.68%, 9.90%, and 8.31%.

What to check on a similar steel mill

For a similar project, measure at the proposed APF connection point under representative rolling conditions before selecting filter capacity.

  1. Record voltage, current, THDi and the harmonic spectrum under representative operating conditions.
  2. Identify the bus or feeder where compensation is required and review the available installation space.
  3. Select APF capacity from the measured harmonic current, allowing for the site's operating margin.

Questions about the case

What does the 600 A figure represent?
It is the total installed APF capacity, not the rolling mill's load-current rating.
Can another steel mill expect THDi below 10%?
The below-10% figure is this project's reported result, not a guaranteed target for every mill. Another site needs its own measurements and filter design.

Compare active harmonic filters for your rolling line.

Start with measured harmonic current and installation requirements when reviewing filter options.

Explore GEYA active harmonic filters
Contact Us

Check Out The Full Catalog

Quick Info Exchange Helps Us Serve You Better
(Low-voltage and solar energy electrical components catalog)

Electrical Equipment catalog