GEYA APPLICATION GUIDE / LOW-VOLTAGE PROTECTION

Garage consumer unit

Garage consumer unit: plan local circuits, solar and EV charging

Understand the role of a local board, explore three connected systems, and prepare a selection brief for a garage, shed or garden office.

A consumer unit receives an electrical supply, distributes it to final circuits and houses devices for isolation and protection. In UK homes, it is often called a fuse box. It may serve lighting, socket outlets and fixed equipment in a house, garage, shed or garden office. These are the core functions described in the IET's consumer-unit guidance.

Consider a garage used as a small workshop, with lighting and sockets inside, solar panels on the roof and an EV charging point beside the door. A local board can organise the everyday circuits. PV and charging add their own equipment and protection requirements. The scene below shows where each belongs and what needs to be considered before selecting the components.

One garage / Three connected systems

See where each protection function belongs.

Choose a tab or a marker to explore the local board, roof solar and EV charging point.

Explore one garage distribution, solar PV and EV charging arrangement A main AC distribution function connects separately to three systems: the garage consumer unit, the PV inverter AC circuit and a dedicated EV supply circuit. Roof PV feeds the inverter through DC isolation. G1 identifies lighting and G2 identifies sockets at the workbench. The outside charge point supplies the parked car. Hollow circles mark functional connection points. Select a G, P or E label to explore that system. This is one example arrangement; the lines show functional connections, not cable routes or terminal wiring. Main AC distribution Example connection point Garage G Workbench G Board G1 G2 PV inverter AC circuit P Roof PV DC isolation P Inverter P EV charging E Dedicated EV supply circuit Parking bay E Charger One example arrangement · functional connections
Example connections: main AC distribution supplies the garage CU and EV circuit; the PV inverter returns AC power to the main distribution Main AC distribution Example connection point
G · Main AC distribution → Garage CU → G1 lighting / G2 sockets.One example arrangement. Lines show functional connections, not cable routes or terminal wiring.
G

A local board for everyday garage circuits

In this example, a designed feeder connects the house distribution system to a consumer unit on the garage's service wall. The local unit provides isolation and distributes power to the planned lighting and socket circuits.

  1. Main AC distribution
  2. Garage consumer unit
  3. Lighting & sockets
Inside the local board Example functions
Q0Main switchLocal isolation
G1RCBOLighting circuit
G2RCBOSocket circuit

Protection at the feeder's origin covers the garage feeder; Q0 provides local isolation; G1 and G2 protect the final circuits. Each RCBO combines overcurrent and residual-current protection. Feeder protection, earthing, device ratings and the complete assembly must be coordinated. Some small outbuildings can be served without a separate local unit.

Read the outbuilding supply guidance

Products by function

GEYA GYR9NE electronic RCBO
GYR9NE electronic RCBO

Residual-current and overcurrent protection for the selected final circuit.

GEYA GYM9H miniature circuit breaker
GYM9H AC MCB

Overload and short-circuit protection where the design uses separate residual-current protection.

The enclosure, busbars and protective devices must be verified as a compatible assembly suitable for the installation conditions. Explore GEYA distribution-box options.

P

Follow roof solar from DC to the AC installation

Roof-mounted PV modules produce DC electricity. The inverter converts it to AC. This example connects its AC circuit to the main AC distribution. A garage consumer unit may be another connection point if the feeder, complete assembly and protection are suitable for generation. The connection point is chosen for the installation, not by the location of the panels alone.

The inverter needs suitable isolation on both sides. DC isolation may be built into the equipment or provided by a separate device, according to the design and manufacturer's instructions. An external switch-disconnector must suit the array's PV DC conditions.

  1. PV array DC
  2. DC isolation
  3. Inverter DC to AC
  4. Main AC distribution This example
PV side
DC isolation, plus array overcurrent and surge protection where the design requires them.
AC side
Isolation and circuit protection selected for the inverter and the possible direction of power flow.
At the board
The designer checks current from all sources, the complete assembly's current rating and arrangement, and device suitability for the intended power-flow direction.

A spare way alone does not establish that a board can accept PV generation. The inverter connection needs a review of the assembly and devices, including suitability for bidirectional power flow. Surge protection is assessed separately from the isolation and conversion stages shown above.

Read the IET guide to PV isolation

The IET also explains bidirectional protective devices and consumer-unit loading with microgeneration.

Products by function

DC-PV2 solar isolator

PV DC isolation, selected for the array voltage, current and switching arrangement.

PV DC circuit breakers

DC overcurrent protection options where required by the array and equipment design.

PV surge protective devices

Surge protection selected for the PV system's DC conditions.

E

Protect the charging circuit and check the charger itself

This example uses a dedicated circuit from the main AC distribution for a Mode 3 AC charging point beside the garage. A suitable garage consumer unit can also supply the charger through its own dedicated final circuit. In either arrangement, the feeder, board and protective devices must support the added load, with an appropriate earthing arrangement and the charger's installation instructions taken into account.

  1. Dedicated EV circuit
  2. Charging equipment
  3. Vehicle

Supply circuit

Overcurrent protection
Upstream RCD protection where required
Earthing and open-PEN assessment, where applicable

Inside the charger

Charging control and switching
Documented RCD functions, where fitted
DC residual-current detection, where fitted

Two residual-current protection routes

Type A/F + RDC-DD
A suitable Type A or F RCD is coordinated with 6 mA smooth DC residual-current detection. The RDC-DD function may be in the charger or provided separately, as the equipment and design permit.
Type B RCD
A suitable Type B RCD is the alternative route for the charging point when selected to cover the expected residual-current waveforms, including smooth DC.

The charger documentation establishes which functions are built in. DC detection alone is not a complete RCD. An MCB protects against overcurrent, while the final RCD arrangement and any upstream RCD requirement are determined for the supply circuit and charger together.

Read the IET explanation of EV RCD functions

Products by function

GYL9-EV RCD

Residual-current protection considered alongside circuit overcurrent protection for an EV charging assembly.

GEYA GYM9H AC miniature circuit breaker
AC MCB families

Overload and short-circuit protection for the selected circuit. The complete EV protection arrangement still needs coordination.

For charger OEMs and panel builders, product selection starts with the equipment specification and the intended assembly.

Does a garage need its own consumer unit?

Not always. A suitably designed circuit from the main building may serve a modest outbuilding without a second consumer unit. Electrical Safety First's outbuilding guidance includes a fused connection unit as one possible supply arrangement when the relevant design criteria have been verified.

A local board becomes useful when the building needs several final circuits, accessible local isolation or room for a planned change in use. The decision starts at the existing installation: available capacity, the proposed feeder route, protective devices and the earthing arrangement determine what is practical. Adding a board at the far end of a cable cannot increase the upstream supply capacity.

For a detached garage, cable selection depends on demand, route length, installation method, voltage drop and fault protection. Earthing and bonding also need a site assessment. Neither a standard cable size nor an earth rod can be prescribed simply because the destination is a garage.

2-way or 4-way garage consumer unit: how much space do you need?

Start with the equipment people will use and the loads likely to run together, then list the final circuits. In the illustrated garage, G1 supplies lighting and G2 supplies general sockets. Fixed workshop equipment may justify another circuit after its load and use have been assessed.

A way is a position for an outgoing circuit; module space is the physical width available for devices. Main switches, RCCBs, RCBOs and SPDs can occupy different widths. Compare the proposed circuits with the manufacturer's usable ways and actual enclosure layout.

Two garage board planning examples
Starting pointPossible circuit schedule
2-way basic garageG1 lighting and G2 general sockets, if these are the only planned final circuits.
4-way small workshopLighting and sockets, with separate circuit positions considered for fixed equipment where the design requires them.

These are planning examples, not standard garage configurations. A larger way count gives more outgoing circuit positions; it does not increase the available supply. For either candidate, check the final circuit schedule, simultaneous demand, feeder capacity and complete assembly rating. For a shed, also consider moisture, dust, condensation and cable entries. For a garden office, account for heating, IT equipment and other loads that may run for long periods.

Product listings may describe an empty enclosure, a board with a main switch, or a populated unit with protective devices already fitted. Check the exact supplied parts, remaining module space, permitted device and busbar combinations, and the manufacturer's installation instructions. A “2-way” or “4-way” label alone does not identify the complete assembly.

A spare way for a future circuit is useful only if the feeder and assembly can support it. It does not establish that an EV charger or PV inverter can be added to the board.

Choose protection for the circuit and the supply

The devices in a consumer unit perform different jobs. The IET's consumer-unit guidance explains the distinction between overcurrent and residual-current protection.

Functions to identify in the proposed assembly
DeviceFunctionSelection boundary
Main switchIsolationDoes not replace circuit protection.
MCBOverload and short-circuit protectionDoes not provide residual-current protection.
RCCBResidual-current protectionHas no integral overcurrent protection.
RCBOResidual-current and overcurrent protectionIts type and ratings must suit the circuit and assembly.
SPDProtection against transient overvoltagesRequires installation-wide assessment and coordination.

A shared RCCB can disconnect all the circuits it protects when it operates. Individual RCBOs can limit the interruption to the affected circuit, subject to upstream protection and coordination. That distinction matters where losing a socket circuit should not also remove the workshop lighting.

The designer considers the connected equipment, expected residual-current waveforms and the protection of both the feeder and final circuits. Surge protection is assessed across the installation, including any PV or charging equipment. It cannot be decided from the box's way count alone.

Match the enclosure to its actual location

The illustrated board sits on a dry, accessible garage wall. An exposed wall or damp shed presents different conditions. Assess moisture, dust, condensation, impact, temperature, cable entries and access for operation and maintenance. An IP rating describes ingress protection; it does not resolve every outdoor issue. The IET's guidance on external consumer units discusses the additional effects of weather and condensation.

There is no universal “IP65 for every outbuilding” rule. The finished assembly needs the protection appropriate to its location, including after cable entries and modifications. An empty enclosure's IP rating alone does not establish the suitability of the installed unit.

Material choice also depends on location. Electrical Safety First's guidance permits an insulated consumer unit meeting the relevant assembly requirements in a detached domestic outbuilding where its construction suits the environment. The assessment includes mechanical damage, stored flammable materials, corrosive conditions and the risk of fire spreading between the outbuilding and the dwelling. This detached-building example is not a blanket rule for every garage.

GEYA's DBS British Distribution Box page lists IP30. Treat that as a model-specific enclosure reference, not evidence of suitability for a damp shed or exposed wall.

Check the enclosure and devices as one assembly

A consumer unit combines its enclosure, busbars, terminals and protective devices. A breaker fitting onto a DIN rail does not prove that it is suitable for the assembly. The manufacturer's declared combinations, temperature-rise limits, short-circuit performance and installation instructions all affect the selection.

BEAMA's device-selection bulletin explains why components must follow the assembly manufacturer's specification. The BS EN IEC 61439-3 standard concerns the integrated distribution board. A standard number on an individual device or box is not evidence for an arbitrary combination.

For an assembled unit, ask for the exact configuration, permitted devices and busbars, ratings, installation instructions and verification records. The product links in the scene identify component functions; the project configuration still needs its own assembly evidence.

Prepare a brief for the installer and supplier

A useful project brief brings the building, supply and equipment requirements together:

  1. Building and location: garage, shed or garden office; attached or detached; indoor or exposed mounting position.
  2. Existing supply: origin, available capacity, proposed feeder route and existing protection.
  3. Loads and circuits: equipment used now, likely simultaneous demand, proposed circuits and realistic future additions.
  4. Environment: moisture, dust, condensation, impact, temperature and cable-entry requirements.
  5. PV or EV equipment: exact inverter or charger model, installation instructions, connection requirements and documented internal protection.
  6. Assembly and verification: earthing and bonding design, device coordination, approved component combinations and required installation records.

Use a competent electrician to design, install, inspect and test the work. For UK projects, the current edition is BS 7671:2018+A4:2026; the previous edition's transition period ended on 15 October 2026. Apply the relevant building requirements and the selected equipment's instructions as well.

To discuss enclosure and protective-device options, send GEYA your project brief. Include the circuit schedule and inverter or charger details so the proposed components can be assessed against the intended assembly.

Plan the garage board around its circuits.

Share the circuit schedule, supply details, mounting location, and any PV inverter or EV charger information. GEYA can discuss enclosure and protective-device options for the proposed assembly.