Factory test case · Active harmonic filtering

Data Center Chiller: 450 A AHF Factory Test

At 100% load in the dual-source test configuration, a 450 A active harmonic filter reduced VFD chiller current THDi from about 31% to 3.84%–4.28%. The test also covered partial-load operation and voltage distortion.

Test boundary The measurements came from a refrigeration equipment manufacturer’s factory test platform, not from an operating data center. They describe recorded test points rather than long-term field performance.
Test setting
Refrigeration equipment manufacturer’s test facility
Equipment under test
VFD-driven chiller intended for high-density cooling applications
Evidence available
Complete before-and-after data at 25% and 100% load in the dual-source test configuration

Project overview

VFD Chiller Test Setup

Engineers evaluated an active harmonic filter for a data center chiller across 25%, 50%, 75% and 100% load under two power-supply configurations.

At the 100% dual-source test point, phase-current THDi measured 30.78%–31.03% before compensation. With a parallel 450 A AHF operating, phase-current THDi measured 3.84%–4.28%.

The system used three 150 A SiC AHF modules. The full test record also captured voltage distortion, current, power factor, harmonic spectrum and waveforms at defined operating points.

Load type
Six-pulse VFD-driven chiller
AHF arrangement
Parallel-connected, 450 A total capacity
Module layout
Three 150 A SiC AHF modules
Primary evidence
Phase-by-phase THDi and THDu before and after compensation at the 25% and 100% dual-source points
Scope limit
Factory test measurements; long-term operating performance was not evaluated

Industry background

Why VFD Chillers Generate Harmonics

Variable-frequency drives allow compressor output to follow changing cooling demand, but the rectifier stage draws nonlinear current. In this test, the six-pulse VFD produced dominant 5th- and 7th-order current harmonics together with higher odd orders.

The engineering question is therefore not only how the chiller performs at full load. Harmonic behavior should be measured at the intended connection point and across the operating range, including partial-load conditions.

For the wider electrical context, see GEYA’s data center power quality solutions.

5th order7th order11th order13th orderhigher odd orders

How the system worked

How the 450 A AHF Was Sized

The test followed a measurement, sizing, parallel compensation and remeasurement sequence.

  1. Measure the operating points

    Voltage, current, harmonic spectrum and waveforms were recorded at defined load points and power-supply configurations.

  2. Estimate the harmonic-current requirement

    For the 100% dual-source operating point, the report used 800 A and approximately 31% THDi as a sizing estimate, giving an approximate harmonic-current allowance of 248 A.

  3. Apply the project factor

    A factor of 1.8 was applied to account for harmonic peak overlap and an assumed high-temperature derating, producing a calculated requirement of approximately 446 A.

  4. Connect the AHF in parallel

    Three 150 A SiC AHF modules were connected at the low-voltage test bus. Current transformers supplied the measurement signal, and the AHF injected compensation current to counter the detected load harmonics.

  5. Repeat measurements across the range

    Post-compensation values were recorded at the remaining load points. Complete before-and-after comparisons were available at the 25% and 100% dual-source points.

800 A × 31%report sizing estimate
≈ 248 Aapproximate harmonic-current allowance
450 Aselected after the 1.8 project factor

This is the report’s project-specific estimate, not a general sizing formula. THDi is referenced to fundamental current, which is different from total RMS current. A new design should use measured harmonic-current data and the selected filter’s operating and derating requirements.

Related GEYA products

The first row records the tested configuration. The GEYA product links below offer options for new projects, with capacity selected from each project’s measurements.

Swipe to view all columns

Product imageProduct or configurationRoleApplication note
—Tested configuration: 3 × 150 A SiC AHF modulesProject-specific 450 A parallel compensation systemSized from the recorded operating data and test assumptions
GY-AHF-SiC active harmonic filter moduleGY-AHF-SiC active harmonic filterGEYA SiC AHF product familyFor new projects where measurements support a modular SiC AHF solution
GEYA active harmonic filter module rangeGEYA active harmonic filter rangeProduct-family comparison and selection pathCompare module and cabinet options after defining the disturbance and installation point

Measured results

Chiller THDi and THDu: Before and After

At 100% load in the dual-source configuration, current THDi fell from 30.78%–31.03% to 3.84%–4.28%. Voltage THDu fell from 11.97%–12.26% to 1.66%–1.73%.

100% Load: Phase-by-Phase Results

Swipe to view all measurements

PhaseTHDi beforeTHDi afterTHDu beforeTHDu after
L131.03%3.84%12.24%1.73%
L230.99%4.28%12.26%1.66%
L330.78%3.90%11.97%1.70%

THDi is total harmonic distortion of current; THDu is total harmonic distortion of voltage. Values above are paired measurements at the 100% dual-source test point.

Current THDi: Before and After

Phase-current THDi before AHF compensation at 100% load in the dual-source chiller factory test.
Before AHF compensationPhase-current THDi was 31.03%, 30.99% and 30.78% at the 100% dual-source test point.
Phase-current THDi after AHF compensation at 100% load in the dual-source chiller factory test.
After AHF compensationPhase-current THDi was 3.84%, 4.28% and 3.90% at the 100% dual-source test point.

Voltage and Current Waveforms: Before and After

Voltage and current waveforms before AHF compensation at 100% load in the dual-source chiller factory test.
Before AHF compensationRecorded voltage and current waveforms at the 100% dual-source test point.
Voltage and current waveforms after AHF compensation at 100% load in the dual-source chiller factory test.
After AHF compensationRecorded voltage and current waveforms at the 100% dual-source test point.

THDi Across the Tested Load Range

Swipe to compare both configurations

LoadDual-source THDi afterSingle-source THDi after
25%5.75%–5.80%5.69%–6.13%
50%4.04%–4.67%4.16%–4.49%
75%4.16%–4.73%4.10%–4.45%
100%3.84%–4.28%3.98%–4.79%

Ranges cover L1–L3 at each recorded test point, not continuous monitoring. Single-source and dual-source identify the two configurations used in the factory report.

25% Load: Before and After

At the dual-source point, THDi changed from 49.24%–50.36% to 5.75%–5.80%, while THDu changed from 3.82%–3.95% to 1.26%–1.39%.

Before-and-after coverage varies by test point

The 25% and 100% dual-source points have complete before-and-after data. Other recorded points provide post-compensation values only.

A higher THDi percentage at light load does not necessarily mean more harmonic current in amperes: the fundamental-current denominator changes with load. See Eaton’s explanation of THD and TDD.

Engineering interpretation

Applying the Results to a New Project

Demonstrated in the recorded test

  • The six-pulse VFD produced a measurable low-order harmonic spectrum.
  • In this factory test, the parallel modular AHF reduced both THDi and THDu at the 25% and 100% dual-source test points.
  • Performance differed between full-load and partial-load conditions.
  • Phase-by-phase values show variation that a single rounded THD value would hide.

Inputs required for a new project

  • Single-line diagram, analyzer export and operating-load profile.
  • Dominant harmonic orders, source configurations and CT location.
  • System voltage and frequency, ambient conditions and installation constraints.
  • Acceptance criteria, the point of common coupling (PCC), maximum demand current and short-circuit data for a compliance assessment.

This test did not measure long-term energy use, service life, maintenance cost or field reliability. Those outcomes require their own measurement plan and operating period.

FAQ

AHF FAQs for VFD Chillers

Why does a VFD-driven chiller produce current harmonics?

The rectifier stage draws current nonlinearly. A six-pulse rectifier typically concentrates distortion in the 5th and 7th orders, with additional higher odd-order components. The actual spectrum should be measured at the intended installation point.

How is an active harmonic filter sized for a VFD chiller?

Use measured harmonic current across the operating range, then account for the selected filter’s installation conditions and compensation duties. The 450 A sizing example shows this report’s estimate and project factor; the project requirements list the inputs needed for a new selection.

Why should THDi be checked at full load and partial load?

THDi is a ratio between harmonic current and fundamental current, so it can change as the load changes. This test recorded different post-compensation ranges at 100% and 25% load in the dual-source configuration, which is why the operating envelope matters.

Does low THDi prove IEEE 519 compliance?

No. THDi uses the fundamental current at the measured operating point; TDD uses maximum demand fundamental current. If IEEE 519 is the project’s acceptance basis, assessment concerns the installation at its applicable PCC, with the required demand-current, short-circuit and measurement data. These chiller test-point THDi values do not establish that assessment.

Will every 800 A chiller require a 450 A active harmonic filter?

No. The 450 A configuration came from this project’s measurements and assumptions. Another chiller may have a different harmonic spectrum, load profile, source condition, installation environment or performance target.