Factory test case · Active harmonic filtering
Data Center Chiller: 450 A AHF Factory Test
At 100% load in the dual-source test configuration, a 450 A active harmonic filter reduced VFD chiller current THDi from about 31% to 3.84%–4.28%. The test also covered partial-load operation and voltage distortion.
- Test setting
- Refrigeration equipment manufacturer’s test facility
- Equipment under test
- VFD-driven chiller intended for high-density cooling applications
- Evidence available
- Complete before-and-after data at 25% and 100% load in the dual-source test configuration
Project overview
VFD Chiller Test Setup
Engineers evaluated an active harmonic filter for a data center chiller across 25%, 50%, 75% and 100% load under two power-supply configurations.
At the 100% dual-source test point, phase-current THDi measured 30.78%–31.03% before compensation. With a parallel 450 A AHF operating, phase-current THDi measured 3.84%–4.28%.
The system used three 150 A SiC AHF modules. The full test record also captured voltage distortion, current, power factor, harmonic spectrum and waveforms at defined operating points.
- Load type
- Six-pulse VFD-driven chiller
- AHF arrangement
- Parallel-connected, 450 A total capacity
- Module layout
- Three 150 A SiC AHF modules
- Primary evidence
- Phase-by-phase THDi and THDu before and after compensation at the 25% and 100% dual-source points
- Scope limit
- Factory test measurements; long-term operating performance was not evaluated
Industry background
Why VFD Chillers Generate Harmonics
Variable-frequency drives allow compressor output to follow changing cooling demand, but the rectifier stage draws nonlinear current. In this test, the six-pulse VFD produced dominant 5th- and 7th-order current harmonics together with higher odd orders.
The engineering question is therefore not only how the chiller performs at full load. Harmonic behavior should be measured at the intended connection point and across the operating range, including partial-load conditions.
For the wider electrical context, see GEYA’s data center power quality solutions.
How the system worked
How the 450 A AHF Was Sized
The test followed a measurement, sizing, parallel compensation and remeasurement sequence.
- Measure the operating points
Voltage, current, harmonic spectrum and waveforms were recorded at defined load points and power-supply configurations.
- Estimate the harmonic-current requirement
For the 100% dual-source operating point, the report used 800 A and approximately 31% THDi as a sizing estimate, giving an approximate harmonic-current allowance of 248 A.
- Apply the project factor
A factor of 1.8 was applied to account for harmonic peak overlap and an assumed high-temperature derating, producing a calculated requirement of approximately 446 A.
- Connect the AHF in parallel
Three 150 A SiC AHF modules were connected at the low-voltage test bus. Current transformers supplied the measurement signal, and the AHF injected compensation current to counter the detected load harmonics.
- Repeat measurements across the range
Post-compensation values were recorded at the remaining load points. Complete before-and-after comparisons were available at the 25% and 100% dual-source points.
This is the report’s project-specific estimate, not a general sizing formula. THDi is referenced to fundamental current, which is different from total RMS current. A new design should use measured harmonic-current data and the selected filter’s operating and derating requirements.
Related GEYA products
AHF Configuration and Product Options
The first row records the tested configuration. The GEYA product links below offer options for new projects, with capacity selected from each project’s measurements.
Swipe to view all columns →
| Product image | Product or configuration | Role | Application note |
|---|---|---|---|
| — | Tested configuration: 3 × 150 A SiC AHF modules | Project-specific 450 A parallel compensation system | Sized from the recorded operating data and test assumptions |
![]() | GY-AHF-SiC active harmonic filter | GEYA SiC AHF product family | For new projects where measurements support a modular SiC AHF solution |
![]() | GEYA active harmonic filter range | Product-family comparison and selection path | Compare module and cabinet options after defining the disturbance and installation point |
Measured results
Chiller THDi and THDu: Before and After
At 100% load in the dual-source configuration, current THDi fell from 30.78%–31.03% to 3.84%–4.28%. Voltage THDu fell from 11.97%–12.26% to 1.66%–1.73%.
100% Load: Phase-by-Phase Results
Swipe to view all measurements →
| Phase | THDi before | THDi after | THDu before | THDu after |
|---|---|---|---|---|
| L1 | 31.03% | 3.84% | 12.24% | 1.73% |
| L2 | 30.99% | 4.28% | 12.26% | 1.66% |
| L3 | 30.78% | 3.90% | 11.97% | 1.70% |
THDi is total harmonic distortion of current; THDu is total harmonic distortion of voltage. Values above are paired measurements at the 100% dual-source test point.
Current THDi: Before and After
Voltage and Current Waveforms: Before and After
THDi Across the Tested Load Range
Swipe to compare both configurations →
| Load | Dual-source THDi after | Single-source THDi after |
|---|---|---|
| 25% | 5.75%–5.80% | 5.69%–6.13% |
| 50% | 4.04%–4.67% | 4.16%–4.49% |
| 75% | 4.16%–4.73% | 4.10%–4.45% |
| 100% | 3.84%–4.28% | 3.98%–4.79% |
Ranges cover L1–L3 at each recorded test point, not continuous monitoring. Single-source and dual-source identify the two configurations used in the factory report.
At the dual-source point, THDi changed from 49.24%–50.36% to 5.75%–5.80%, while THDu changed from 3.82%–3.95% to 1.26%–1.39%.
The 25% and 100% dual-source points have complete before-and-after data. Other recorded points provide post-compensation values only.
A higher THDi percentage at light load does not necessarily mean more harmonic current in amperes: the fundamental-current denominator changes with load. See Eaton’s explanation of THD and TDD.
Engineering interpretation
Applying the Results to a New Project
Demonstrated in the recorded test
- The six-pulse VFD produced a measurable low-order harmonic spectrum.
- In this factory test, the parallel modular AHF reduced both THDi and THDu at the 25% and 100% dual-source test points.
- Performance differed between full-load and partial-load conditions.
- Phase-by-phase values show variation that a single rounded THD value would hide.
Inputs required for a new project
- Single-line diagram, analyzer export and operating-load profile.
- Dominant harmonic orders, source configurations and CT location.
- System voltage and frequency, ambient conditions and installation constraints.
- Acceptance criteria, the point of common coupling (PCC), maximum demand current and short-circuit data for a compliance assessment.
This test did not measure long-term energy use, service life, maintenance cost or field reliability. Those outcomes require their own measurement plan and operating period.
FAQ
AHF FAQs for VFD Chillers
Why does a VFD-driven chiller produce current harmonics?
The rectifier stage draws current nonlinearly. A six-pulse rectifier typically concentrates distortion in the 5th and 7th orders, with additional higher odd-order components. The actual spectrum should be measured at the intended installation point.
How is an active harmonic filter sized for a VFD chiller?
Use measured harmonic current across the operating range, then account for the selected filter’s installation conditions and compensation duties. The 450 A sizing example shows this report’s estimate and project factor; the project requirements list the inputs needed for a new selection.
Why should THDi be checked at full load and partial load?
THDi is a ratio between harmonic current and fundamental current, so it can change as the load changes. This test recorded different post-compensation ranges at 100% and 25% load in the dual-source configuration, which is why the operating envelope matters.
Does low THDi prove IEEE 519 compliance?
No. THDi uses the fundamental current at the measured operating point; TDD uses maximum demand fundamental current. If IEEE 519 is the project’s acceptance basis, assessment concerns the installation at its applicable PCC, with the required demand-current, short-circuit and measurement data. These chiller test-point THDi values do not establish that assessment.
Will every 800 A chiller require a 450 A active harmonic filter?
No. The 450 A configuration came from this project’s measurements and assumptions. Another chiller may have a different harmonic spectrum, load profile, source condition, installation environment or performance target.